Industrial 15" Flat Panel Monitor
Publication 6185-5.1
To calibrate the monitor:
1.
Start the flat panel adjustment utility included with the monitor. For
instructions on starting the utility, refer to Page 18.
2.
Press and hold down both dimmer buttons for eight seconds.
Note:
The screen will go blank after two seconds and will
come back on after eight seconds.
The amber LED blinks slowly to indicate that you are in calibration
mode.
3.
Press the right dimmer button to adjust the contrast value to its
highest setting. The gray bars on the bottom of the screen image
change to white.
4.
Use the left dimmer button to lower the contrast until the white bar
stays white and the first light gray bar changes back to light gray.
This is the optimal setting for the video gain. (Refer to Figure 9 on
Page 22.)
5.
Press and hold down both dimmer buttons for 2 seconds to exit
calibration mode.
The amber light blinks twice to indicate that the calibration is
complete.