
22
Rockwell Automation Publication 48CR-UM001A-EN-P - November 2019
Chapter 4
Configure for EtherNet/IP Network
Restore Device Defaults Via Hardware
If a software default and reset is not possible, it may be necessary to reset the code
reader by shorting (connecting) specific pins.
1.
Apply power to the code reader.
2.
Locate Pin 3 (Default) and Pin 7 (Ground) on the connector. Access
depends on wiring configuration. This step may require an accessory cable
3.
Momentarily connect the wires (or pins).
4.
Within 3 seconds, disconnect and then reconnect the two wires again.
Restore Device Defaults Via WebConnect
1.
From the Start view, click the gear icon to open the Application Settings
menu.
2.
Click the Restore Default Settings button.
IMPORTANT
For this reset to occur, this command must be executed within 60 seconds of
a power-on or a reset.
ATTENTION:
Verify that the correct pins are located. If you connect the
wrong pins, damage to the code reader can occur.
1
2