Publication 1769-UM002B-EN-P - July 2005
4-10
Module Data, Status, and Channel Configuration for the Output Modules
If this selection is enabled [the bit is set (1)] and the system enters the program
mode, it commands the module to convert the
user-specified
value from the
channel’s program/idle value word (3 or 5) to the appropriate analog output
for the range selected.
1769-OF2 Program/Idle to Fault Enable (PFE0 and PFE1)
If a system currently in program/idle mode faults, this setting (word 0, bit 0;
word 1, bit 0) determines whether the program/idle or fault mode value is
applied to the output. If the selection is enabled [the bit is set (1)], the module
applies the fault mode data value. If the selection is disabled [the bit is reset
(0)], the module applies the program/idle mode data value. The default setting
is disabled.
EXAMPLE
•
If the default value, 0000, is used and the range selected
is 0 to 20 mA, the module will output 0 mA for all data
formats.
•
If the raw/proportional or engineering units format is
selected and zero is entered as the program/idle value
in either a 1 to 5V dc or 4 to 20 mA range, a
configuration error results.
•
See Table 4.5 1769-OF2 Valid Output Data Table on
page 4-12 for more examples.
TIP
Not all controllers support this function. Refer to your
controller’s user manual for details.
TIP
Not all controllers support this function. Refer to your
controller’s user manual for details.
Summary of Contents for Allen-Bradley 1769-IF4
Page 1: ...CompactI OAnalog Modules 1769 IF4 IF8 OF2 OF8C and OF8V User Manual ...
Page 4: ...Publication 1769 UM002B EN P July 2005 Summary of Changes 2 Notes ...
Page 10: ...Publication 1769 UM002B EN P July 2005 Table of Contents vi ...
Page 14: ...Publication 1769 UM002B EN P July 2005 4 Notes ...
Page 183: ......