6
Rockwell Automation Publication 1606-RM100A-EN-P - July 2020
Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual
Specifications
Catalog Numbers
Terminology and
Abbreviations
Attribute
Value
Notes
Output voltage
24V DC
Nominal
Adjustment range
24…28V
Factory setting 24.1V
Output current
6.0…5.1 A
Below 45 °C (113 °F) ambient
5.0…4.3 A
At 60 °C (140 °F) ambient
3.8…3.2 A
—
Derate linearly 45…70 °C (113…158 °F)
Input voltage AC
AC 100…240V
-15%/+10%
Mains frequency
50…60 Hz
±6%
Input current AC
1.09/0.6 A
At 120/230V AC
Power factor
0.98/0.91
At 120/230V AC
Input voltage DC
DC 110…150V
±20%
For 1606-XLE120E, 1606-XLE120EC, 1606-XLE120EL,
1606-XLE120EH
DC 110…300V
±20%
For 1606-XLE120ED
Input current DC
1.21/0.43 A
At 110/300V DC
AC Inrush current
4/4 A
At 120/230V AC
Efficiency
93.6/94.3%
At 120/230V AC
Losses
8.2/7.3 W
At 120/230V AC
Hold-up time
35/ 35 ms
At 120/230V AC
Temperature range
-25…+70 °C (-13…+158 °F)
—
Size (WxHxD)
32x124x102 mm (1.26x4.88x4.02 in.)
Without DIN rail
Weight
440 g (0.97 lb)
—
Power Supply
Connection
1606-XLE120E
Screw terminals
1606-XLE120EC
Screw terminals and conformal coated pc-boards
1606-XLE120EL
Spring-damp terminals
1606-XLE120EH
Push-in terminals
1606-XLE120ED
Screw terminals and enhanced DC input
Term
Definition
PE and symbol
PE is the abbreviation for
P
rotective
E
arth and has the same meaning as the symbol.
Earth, Ground
This document uses the term ‘earth’ which is the same as the U.S. term ‘ground.’
AC 230V
A figure that is displayed with the AC or DC before the value represents a nominal voltage
with standard tolerances (usually ±15%) included. For example: DC 12V describes a 12V
battery disregarding whether it is full (13.7V) or flat (10V).
230V AC
A figure with the unit (V AC) at the end is a momentary figure without any additional
tolerances included.
50 Hz vs. 60 Hz
As long as not otherwise stated, AC 230V parameters are valid at 50 Hz mains frequency.