Rockwell Automation Publication 1606-RM100A-EN-P - July 2020
7
Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual
AC Input
The device is suitable to be supplied from TN, TT, or IT mains networks with
AC voltage. For suitable DC supply voltages,
Attribute
Value
Notes
AC input
Nom
AC 100-240V
—
AC input range
Min
85-264V AC
Continuous operation
Min
264-300V AC Occasionally for maximal 500 ms
Allowed voltage L or N to earth
Max
300V AC
Continuous, according to IEC 60664-1
Input frequency
Nom
50…60 Hz
±6%
Turn-on voltage
Typ
80V AC
Steady-state value, see
Shut-down voltage
Typ
74V AC
Steady-state value, see
External input protection
See
Installation Instructions on page 6
.
AC 100V
AC 120V
AC 230V
Input current
Typ
1.30 A
1.09 A
0.60 A
At 24V, 5 A, see
Power factor
Typ
0.99
0.98
0.91
At 24V, 5 A, see
Crest factor
Typ
1.7
1.8
2.2
At 24V, 5 A, The crest factor is the mathematical ratio of the peak value to RMS value of the input current
waveform.
Startup delay
Typ
420 ms
380 ms
385 ms
See
Rise time
Typ
80 ms
80 ms
80 ms
At 24V, 5 A constant current load, 0 mF load capacitance, see
Typ
100 ms
100 ms
110 ms
At 24V, 5 A constant current load, 5 mF load capacitance, see
Max
200 mV
200 mV
200 mV
See
Figure 1 - Input Voltage Range
Figure 2 - Turn-on Behavior, Definitions
Figure 3 - Input Current Versus Output Current at 24V Output Voltage
Figure 4 - Power Factor Versus Output Current at 24V Output Voltage