Rockwell Automation Publication 1606-RM100A-EN-P - July 2020
29
Power Supply - 24V, 5 A, 120 W, Single-phase Input Reference Manual
Mounting Orientations
Mounting orientations other than input terminals on the bottom and output
on the top require a reduction in continuous output power or a limitation in
the maximum allowed ambient temperature.
The listed lifetime and MTBF values from this datasheet apply only for the
standard mounting orientation. The following curves give an indication for
allowed output currents for altitudes up to 2000 m (6560 ft).
Figure 41 - Mounting
Orientation A (Standard
Orientation)
Figure 42 - Mounting
Orientation B (Upside
Down)
Figure 43 - Mounting
Orientation C (Table-top
Mounting)
Figure 44 - Mounting
Orientation D (Horizontal
CW)
Figure 45 - Mounting
Orientation E (Horizontal
CCW)