Rockwell Automation Publication 150-UM009E-EN-P - August 2021
21
Chapter 3 Programming
Motor FLA Requirements
The front of the SMC controller contains a dial that is used for setting the
actual FLA of the motor. The label is designed to accommodate motors
connected in the line or Delta mode. To determine the proper setting, look at
the motor’s nameplate and set the dial accordingly. The dial setting can be
modified depending on the service factor of the motor.
Figure 11 - Motor FLA Setting
Table 13 - Overload Trip Class
Setting
Switch #11
Switch #12 Description
OFF
OFF
OFF
The controller incorporates, as standard, electronic overload
protection. This motor overload protection is accomplished
electronically by using internal current transformers on each of the
three phases.
10
ON
OFF
15
OFF
ON
20
ON
ON
Table 14 - Overload Reset
Setting
Switch #13 Description
Manual
OFF
In manual reset mode, the fault can only be reset by pushing the ‘Push to Reset’ button
on the front of the controller. In auto reset mode, the unit automatically resets when
the unit determines the motor has cooled to 75% of its thermal capacity.
Auto
ON
Table 15 - Aux #1 Setting
Setting
Switch #14 Description
Normal
OFF
The operation defines the operation of the auxiliary contacts. Normal mode means
that the contact changes state immediately when a start/run command is given.
Up-to-Speed mode means that the contact changes state only when the controller
is in bypass. Aux#2, when added, operates opposite of this programming.
Up-to-Speed
ON
Table 16 - Motor Connection Type
Setting
Switch #15 Description
Delta
OFF
In Delta connection mode, the device is designed to control a 6- or 12-lead motor. In line
connection mode, the device is designed to control a 3- or 9-lead motor.
Line
ON
Table 17 - Stop Delay
Setting [seconds]
Switch #16 Description
0.0
OFF
When the delay is programmed, the motor continues to run for the
programmed period of time after the run command is removed from the
controller.
0.75
ON
∆ 32
19
Delta FLA
Line FLA
∆ 11
7
∆ 22
13
Service Factor _ _
FLA _ _
Service Factor < 1.15
Service Factor ≥ 1.15
= 0.9 X FLA
= 1.0 X FLA
= 1.0 X FLA
OR
Maximum Continuous Rated
(MCR) Motors