Rockwell Automation Publication 150-UM009E-EN-P - August 2021
13
Chapter 2 Installation and Wiring
Table 6 - Fault Contactor Torque
Controller Size [A]
Attribute
Power Terminals
Line
Load
Control
32/51/64
Cat. No. 150-E40KD00
Wire size
10…2 AWG
6…35 mm
2
10…2 AWG
6…35 mm
2
18…14 AWG
1…2.5 mm
2
Torque
35 lb•in
4 N•m
35 lb•in
4 N•m
11 lb•in
1.2 N•m
74/104
Cat. No. 150-E65KD00
Wire size
10…2 AWG
6…35 mm
2
10…2 AWG
6…35 mm
2
18…14 AWG
1…2.5 mm
2
Torque
35 lb•in
4 N•m
35 lb•in
4 N•m
11 lb•in
1.2 N•m
147
Cat. No. 150-E80KD00
Wire size
6…1 AWG
6…70 mm
2
6…1 AWG
6…70 mm
2
18…14 AWG
1…2.5 mm
2
Torque
53 lb•in
6 N•m
53 lb•in
6 N•m
11 lb•in
1.2 N•m
234
Cat. No. 150-E190KD00
Wire size
6…300 MCM
10…150 mm
2
6…300 MCM
10…150 mm
2
18…14 AWG
1…4 mm
2
Torque
300 lb•in
34 N•m
300 lb•in
34 N•m
8.9…10.6 lb•in
1…1.2 N•m