Troubleshooting
Extended Local I/O
5-50
The following table describes each bit in word 23 (Channel status and Media bits) of the diagnostic file.
Maximum number of simultaneously used
unconnected servers (always less than or equal to
20)
59
Accumulated number of dropped unconnected requests
61
Accumulated number of unconnected server
time-outs
60
Accumulated number of JITT overruns
62
1
The file offset in the user-specified ControlNet diagnostics file. For example, if you specified N12, then the Buffer Errors would be located in N12:0, bits 15 - 00.
Bit(s):
Description:
Values:
2 - 0
channel A LED state
000 = off
001 = green
010 = flashing green/off
011 = flashing red/off
100 = flashing red/green
101 = railroading red/off
110 = railroading red/green
111 = red
5 - 3
channel B LED state
6
redundancy warning
0 = normal
1 = non-selected channel is unusable
7
active channel
0 = channel B active
1 = channel A active
8
repeater mode
0 = device set for normal mode
1 = device set for repeater mode
9
channel A media mode
0 = configured for Coaxial
1 = configured for fiber
10
channel B media mode
0 = configured for Coaxial
1 = configured for fiber
15 - 11
reserved
Field Names
File Offset
1
(word;bits)
Field Names
File Offset
1
(word;bits)
Fault Codes