Switch Settings
Remote I/O Rack Number 4-16
Classic PLC-5
processors only
Remote I/O Rack Number
Classic PLC-5 Processor (except PLC-5/10) as an Adapter in a PLC-5,
Scanner Module, or VME System
Rack
4
5
6
7
8
Rack
4
5
6
7
8
01
on
on
on
on
off
15
on
off
off
on
off
02
on
on
on
off
on
16
on
off
off
off
on
03
on
on
on
off
off
17
on
off
off
off
off
04
on
on
off
on
on
20
off
on
on
on
on
05
on
on
off
on
off
21
off
on
on
on
off
06
on
on
off
off
on
22
off
on
on
off
on
07
on
on
off
off
off
23
off
on
on
off
off
10
on
off
on
on
on
24
off
on
off
on
on
11
on
off
on
on
off
25
off
on
off
on
off
12
on
off
on
off
on
26
off
on
off
off
on
13
on
off
on
off
off
27
off
on
off
off
off
14
on
off
off
on
on
PLC-5/15, -5/20, -5/20E, -5/20C processors address racks 01-03PLC-5/40, -5/40L, -5/40E, -5/40C processors address racks 01-17
PLC-5/11 processor address rack 3 only (as remote I/O) PLC-5/60, -5/60L, -5/80, -5/80E, -5/80C processors address
PLC-5/25, -5/30 processors address racks 01-07racks 01-27
on = closed
off = open