67
1756-SG001G-EN-P — March 2004
Step 6 - Select:
y
one power supply for each chassis
y
a power supply bundle if you are planning a
redundant power supply system
Selecting Power Supplies
ControlLogix power supplies are used with the 1756 chassis to provide 1.2V, 3.3V,
5V, and 24V dc power directly to the chassis backplane. Non-redundant (1756-PA72,
-PB72, -PA75, -PB75) and redundant (1756-PA75R, -PB75R) power supplies are
available.
Selecting a standard power supply
You mount a standard power supply directly on the left end of the chassis, where it
plugs directly into the backplane. The power supply you select can determine which
chassis you can use.
Specification
Power Supplies
1756-PA72
1756-PA75
1756-PB72
1756-PB75
1756-PC75
1756-PH75
Nominal Input Voltage
120V ac or 220V ac
24V dc
48V dc
125V dc
Input Voltage Range
85…265V ac
19…32V dc
30...60V dc
90...143V dc
Maximum Real Input Power
95 W
97 W
98 W
95 W
Maximum Apparent Input Power
240 VA
na
na
na
Maximum Transformer Load
238 VA
na
na
na
Input Frequency
47…63 Hz
dc
dc
dc
Maximum Backplane Output Current
1.5A @ 1.2V dc
4A @ 3.3V dc
10A @ 5V dc
2.8A @ 24V dc
75W total
1.5A @ 1.2V dc
4A @ 3.3V dc
13A @ 5V dc
2.8A @ 24V dc
75W total
1.5A @ 1.2V dc
4A @ 3.3V dc
10A @ 5V dc
2.8A @ 24V dc
75W total
1.5A @ 1.2V dc
4A @ 3.3V dc
13A @ 5V dc
2.8A @ 24V dc
75W total
1.5A @ 1.2V dc
4A @ 3.3V dc
13A @ 5V dc
2.8A @ 24V dc
75W total
1.5A @ 1.2V dc
4A @ 3.3V dc
13A @ 5V dc
2.8A @ 24V dc
75W total
Hold Up Time
✶
60 Hz
85V ac: 2 cycles
120V ac: 6 cycles
220V ac: 20 cycles
20ms @ 19V dc
70ms @ 24V dc
50 ms @ 30...60V dc
50ms @ 90...143V dc
Chassis Compatibility
series A
series B
series B
series A
series B
series B
series B
series B
Location
left side of chassis
left side of chassis
left side of chassis
left side of chassis
Certifications:
UL, CSA (Class I, Division 2, Group A, B, C, D), CE, FM, C-Tick
✶
The hold up time is the time between input voltage removal and dc power failure.
†This can be a maximum of 0.91 cable-metered (3 cable feet) from the ControlLogix chassis.
Summary of Contents for 1756-L55M12
Page 1: ...ControlLogix Selection Guide 1756 L55 1756 L61 1756 L62 1756 L63 1756 L60M03SE...
Page 67: ...65 1756 SG001G EN P March 2004 1756 A7 with power supply 1756 A10 with power supply...
Page 68: ...66 1756 SG001G EN P March 2004 1756 A13 with power supply 1756 A17 with power supply...
Page 72: ...70 1756 SG001G EN P March 2004 Power load and transformer sizing...