34
1756-SG001G-EN-P — March 2004
Select the appropriate Ethernet interface:
Ethernet interfaces
If your application does this:
Select this interface:
Description:
y
controls I/O modules
y
requires an adapter for disibuted I/O on
EtherNet/IP links
y
communicates with other EtherNet/IP
devices (messages)
y
bridges EtherNet/IP links to route messages
to devices on other networks
1756-ENBT
The EtherNet/IP communication module:
y
control I/O over an EtherNet/IP network
y
acts as an adapter for disitributed I/O on
remote EtherNet/IP links
y
bridge EtherNet/IP links to route messages
to devices on other networks
y
requires remote access via Internet browser
to tags in a local ControlLogix controller
y
communicates with other EtherNet/IP
devices (messages)
y
bridges EtherNet/IP links to route messages
to devices on other networks
1756-EWEB
The enhanced web server module provides
Internet browser access to ControlLogix
controllers so you can monitor and modify
data remotely via XML web pages. The web
server module supports:
y
data access (read and write) to
ControlLogix controllers
y
bridging and routing of messages
y
custom web pages
y
email capability
Cat. No.
Communication Rate
ConnectionsConnections
Power Dissipation, Max.
Backplane Current (mA) at 5V
Backplane Current (mA) at 24V
1756-ENBT
10/100 Mbps
Each module supports a maximum
of:
y
64 TCP/IP connections
y
128 Logix connections (I/O and
information
y
5000 messages/second
3.65 W
700 mA
3 mA
1756-EWEB
3.65 W
700 mA
3 mA
Certifications:
UL, CSA (Class I, Division 2, Group A, B, C, D), CE, FM, C-Tick
ETHERNET
ETHERNET
FAUL
AULT
RS232
RS232
NET
NET
TX/RX
TX/RX
TX/RX
TX/RX
PWR
PWR
CABLE
CABLE
EXTERNAL
EXTERNAL
IP
IP
Summary of Contents for 1756-L55M12
Page 1: ...ControlLogix Selection Guide 1756 L55 1756 L61 1756 L62 1756 L63 1756 L60M03SE...
Page 67: ...65 1756 SG001G EN P March 2004 1756 A7 with power supply 1756 A10 with power supply...
Page 68: ...66 1756 SG001G EN P March 2004 1756 A13 with power supply 1756 A17 with power supply...
Page 72: ...70 1756 SG001G EN P March 2004 Power load and transformer sizing...
Page 85: ...83 1756 SG001G EN P March 2004 Notes...
Page 86: ...84 1756 SG001G EN P March 2004 Notes...
Page 87: ......