8
SmartGuard 600 Controllers
Publication 1752-IN001C-EN-P - January 2009
Set the communication rate by using the DIP switch on the front of the controller.
Set the IP Address for Ethernet Communication
Connect the 1752-L24BBBE controller to the network via a 100 Mbps Ethernet
switch, which will help reduce collisions and lost packets, and increase bandwidth.
The 1752-L24BBBE controller is shipped with BOOTP enabled for setting the IP
address. You can use any commercially available BOOTP server. If you do not have
BOOTP Server capabilities on your network, download the free Rockwell
Automation BOOTP server from
http://www.ab.com/networks/bootp.html
.
To set the IP address by using the Rockwell Automation BOOTP utility, follow
these steps.
1. Run the BOOTP utility.
2. Double-click the hardware address of the device you want to configure.
DIP Switch Settings
DIP Switch
Pin
1
2
3
4
Communication Rate
OFF
OFF
OFF
OFF
125 Kbps
ON
OFF
OFF
OFF
250 Kbps
OFF
ON
OFF
OFF
500 Kbps
ON
ON
OFF
OFF
Set by software
ON or OFF
ON or OFF
ON
OFF
Set by software
ON or OFF
ON or OFF
ON or OFF
ON
Automatic baud-rate detection
IMPORTANT
If you change the communication rate of your network, make sure that all devices change
to the new communication rate. Mixed communication rates produce communication
errors.