![Rockwell Automation 1752-L24BBB Installation Instructions Manual Download Page 27](http://html.mh-extra.com/html/rockwell-automation/1752-l24bbb/1752-l24bbb_installation-instructions-manual_1475366027.webp)
SmartGuard 600 Controllers
27
Publication 1752-IN001C-EN-P - January 2009
EFT/B immunity
IEC 61000-4-4:
•
±2 kV @ 5 kHz on power
ports
•
±2 kV @ 5 kHz on signal
ports
•
±2 kV @ 5 kHz on
communication ports
IEC 61000-4-4:
•
±2 kV @ 5 kHz on power
ports
•
±1 kV @ 5 kHz on signal
ports
•
±1 kV @ 5 kHz on
communication ports
Surge transient immunity
IEC 61000-4-5:
•
±1 kV line-line (DM) and ±2
kV line-earth (CM) on power
ports
•
±1 kV line-line (DM) and ±2
kV line-earth (CM) on signal
ports
•
±1 kV line-earth (CM) on
communication ports
IEC 61000-4-5:
•
±500V line-line (DM) and ±1
kV line-earth (CM) on power
ports
•
±1 kV line-earth (CM) on
signal ports
•
±1 kV line-earth (CM) on
communication ports
Conducted RF immunity
IEC 61000-4-6:
•
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification
(1)
(when product is marked)
Value
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified
for US and Canada. See UL File E194810.
CE
European Union 2004/108/EEC EMC Directive, compliant with:
•
EN 61000-6-4; Industrial Emissions
•
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
•
EN 61326-1; Meas./Control/Lab., Industrial Requirements
•
EN 61000-6-2; Industrial Immunity
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
TÜV
TÜV Certified for Functional Safety
Functional Safety: SIL 1 to 3, according to IEC 61508; Performance Level PL(e)
according to ISO 13849-1, Category 1 to 4, according to EN954-1; NFPA79;
when used as described in the SmartGuard Controllers Safety Reference
Manual, publication
1752-RM001
.
UL
UL Certified for Functional Safety. See UL File E256621.
Environmental Specifications
Attribute
1752-L24BBB
1752-L24BBBE