External auger:
1.
Install the auger output over the burner.
2.
Auger should be at an angle between 40 and 50 degrees.
3.
The flexible hose should be angled enough as to allow for
the free passage of the wood pellets to the burner without
getting stuck in the PVC hose.
Temperature sensor on the boiler:
Mount the sensor within a sufficiently long thermostat pocket.
Secure sensor to prevent accidental slippage.
Safety thermostat:
Mount on either the left or right side of the boiler as displayed
in image.
Note
: Functional testing of the high limit safety
thermostat is required before starting up the boiler. To test,
press moderately on the disc (shown in A) in the direction
towards the temperature feeler. A small "click“ will occur, signalling
that the connection between C and C2 is
interrupted and that the high limit safety
thermostat is triggered, to reset the
thermostat press hard on the red button
marked (B) in the drawing. You will also hear
a "click", signalling that the connection
between C and C2 is restored and that the high limit safety thermostat
is activated and ready for use.