Electrical installer
32
4
Table 4.1
CAN bus cables type
CABLE NAME
SIGNALS / COLOR
MAX LENGTH
Note
Robur
Ordering Code OCVO008
ROBUR NETBUS
H= BLACK
L= WHITE
GND= BROWN
450 m
Honeywell SDS 1620
In all cases the fourth conductor should not be
used
BELDEN 3086A
H= BLACK
L= WHITE
GND= BROWN
450 m
TURCK type 530
DeviceNet Mid Cable
TURCK type 5711
H= BLUE
L= WHITE
GND= BLACK
450 m
Honeywell SDS 2022
TURCK type 531
H= BLACK
L= WHITE
GND= BROWN
200 m
How to connect the CAN bus cable to the appliance
To connect the CAN bus cable to the AY10 electronic board
(Paragraph 1.5
p. 18, located in the electrical panel inside the
AY00-120 unit, Figure 4.3
p. 32, Details A and B:
1. Access the electrical board of the appliance according to the
Procedure 4.2
2. Connect the CAN bus cable to terminals GND, L and H (shield-
ing/ea two signal conductors) of the AY10 board.
3. Place the Jumper J1, of the AY10 board, OPEN.
4. Connect the DDC to the CAN bus cable to terminals GND, L
and H (shielding/ea two signal conductors) of the
DDC.
5. The CAN bus connection between the AY10 board and the
S61 board is pre-wired (Figure 1.14
Figure 4.3
CAN-BUS connection between Gitié and DDC
DDC
Direct Digital Control
SCH5
S70+AY10 electronic boards
J1
Jumpers CAN-BUS on AY10 board
J21
Jumper CAN-BUS in board DDC
A
Terminal node connection - (3 wires; J21 jumpers = "closed")
B
Intermediate node connection - (3 wires; J1 jumpers ="open")
H,L,GND Data signal wires (ref. cables table)
A
B
SCH5
DDC
GND
H L
JUMPER J21
P8
Place the CLOSED J21 Jumpers (Detail A) if the node is terminal
(one connected CAN bus cable section only), or OPEN (Detail
B) if the node is intermediate (two connected CAN bus cable
sections).
Figure 4.4
Connection of the CAN bus cable to the control panel
DDC
Direct Digital Control
GND
Common data
L
Data signal LOW
H
Data signal HIGH
J21
Jumpers CAN bus on DDC board
A
Detail of "terminal node" case (3 wires; J21 = jumper "closed")
B
Detail of "intermediate node" case (3 wires; J21 = jumper "closed")
P8
CAN port/connector
DDC
DDC
GND
H L
JUMPER J21
P8
GND
H L
JUMPER J21
P8
B
A
4.4.2
Control with external enables
How to connect external enables
Connection of external requests is effected on the termi-
nal block located in the electrical panel inside the AY00-
120 unit.
It is required to arrange:
▶
Request devices (e.g. thermostats, timers, buttons, ...) fitted
with voltage-free NO contacts.
If you wish the heating enables of the two units to be simultane-
ous follow the connection diagram shown in Figure 4.5
Should you wish the enables of the two units to be independent
follow the connection diagram shown in Figure 4.6