Heating engineer
26
3
Figure 3.1
Hydraulic diagram Gitié ARAY /2 C0
1
Anti-vibration connection
2
Pressure gauge
3
Flow regulator valve
4
Water filter
5
Shut-off valves
6
3 bar safety valve
7
Expansion tank
8
Hydraulic separator / buffer tank
9
Outdoor water pump (primary circuit)
10 Water pump (secondary circuit)
A
Gas connection
A
9
1
2
3
4
5
7
6
10
8
P
P
Figure 3.2
Hydraulic diagram Gitié ARAY /4 C0 ACS
1
Anti-vibration connection
2
Pressure gauge
3
Flow regulator valve
4
Water filter
5
Shut-off valves
6
3 bar safety valve
7
Expansion tank
8
Buffer tank (and hydraulic separator)
9
Water pump (secondary circuit)
10 Check valve
11 Thermostat with adjustable differential for
DHW
12 DHW accumulation tank
13 Thermostat with adjustable differential for
Legionella function
14 3-way diverter valves for DHW
15 DDC
16 RB100
17 Outdoor temperature probe
18 Outdoor water pump (boiler primary circuit)
19 Outdoor water pump (GAHP primary circuit)
A
Gas connection
B
Conditioning and heating system
C
Water mains
D
DHW
15
12
9
10
16
A
14
1
6
7
3
4
5
2
8
13
17
18
19
B
11
C
D
P
P
P
P
T
3.4
WATER CIRCULATION PUMPS
3.4.1
Versions C0
Circulation pumps (flows and heads) must be selected and in-
stalled based on pressure losses of hydraulic circuits (
comp exchange ter appliance).
For the appliance pressure losses refer to Table 1.2
Design Manual.
Circulation pumps will be controlled at constant flow.
For pump sizing in the version KIT/2 C0 also consider the
alternate operation case.
For electrical connections of the pumps refer to Paragraph
4.5
3.4.2
Versions C1
Water circulation pumps are supplied on the appliance.
For available water flow and residual head features refer to Table
1.2
p. 21 and Design Manual.
3.5
ANTIFREEZE FUNCTION
Active antifreeze self-protection
The appliance is equipped with an active antifreeze