ACF60-00 – Installation, User’s and Maintenance Manual
12
Ed. 04/2012
ACF60-00, ACF60-00 S – COOLING CAPACITY CORRECTION FACTORS
Table 3
–
ACF60-00, ACF60-00 S – Cooling capacity multiplication correctional factors for external air
temperatures and water flow rates different from the nominal values reported in the table.
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
3.0
5.0
7.0
9.0
0
0.98
0.99
1.01
1.03
5
0.98
0.99
1.01
1.03
10
0.98
0.99
1.01
1.03
15
0.98
0.99
1.01
1.03
20
0.98
0.99
1.01
1.03
25
0.97
0.99
1.01
1.03
30
0.90
0.98
1.01
1.03
35
0.67
0.87
1.00
1.02
40
—
—
0.88
0.93
45
—
—
0.67
0.78