Section GENERAL INFORMATION AND TECHNICAL SPECIFICATIONS
Ed. 04/2012
25
PED Characteristics
The ACF60-00 chiller has a pressurized hermetic circuit and is therefore subject to the to
the Pressurized Equipment Directive (PED).
The corresponding parameters and value are reported in the following table:
ACF60-00 ACF60-00 HR ACF60-00 TK ACF60-00 HT ACF60-00 LB
PARAMETERS
FLUID CONTENT CHARACTERISTICS
FLUID CONTENT
H
2
O + NH
3
CHARGE
kgH
2
O
kgNH
3
10
7.5
10
7.5
10
8.5
10.5
7.5
10.5
7.2
FLUID GROUP
1°
PRESSURE
MAXIMUM
ALLOWABLE
PRESSURE
bar
35
SAFETY VALVE
CALIBRATION
PRESSURE
bar
35
TEST PRESSURE
(in air)
bar
55
VOLUME
GENERATOR
litres
18.6
LEVELING
CHAMBER
litres
11.5
SOLUTION PUMP
litres
3.3
SCA
litres
6.3
EVAPORATOR
litres
3.7
RECOVERY UNIT
litres
3.7
COOLANT
VOLUME
VARIATOR
litres
4.5
TARE AND FILLING RATIO
TARE kg
kg
220
230
FILLING RATIO
kg(NH
3
)/
L
0.173
0.159
0.177
0.157
0.150
Table 16 –
PED characteristics of the ACF’s hermetic circuit. Empty grey boxes: element not available.
Summary of Contents for GA ACF60-00
Page 4: ......
Page 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Page 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Page 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Page 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Page 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Page 93: ...APPENDIX Ed 04 2012 89 ...
Page 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Page 95: ......