Installation, Operation and Maintenance Manual - Ed.07/2005
EVOLUZIONE series natural gas/LPG heaters
Figure 13
– POSITIONS OF WALL-MOUNTED TERMINAL
3.3.4 WALL INSTALLATION
For the installation of its Evoluzione heaters, ROBUR S.p.A. supplies various types of mounting brackets (as
optional extras) from which to choose according to the type of exhaust outlet to be created. In particular:
- upper mounting bracket. This supports the heater from above, and is supplied complete with condensate
drain and air/exhaust gas pipe connection kit with elements for drawing air/exhaust gas (see Figure 31).
- upper mounting bracket with integrated wall-mounted outlets (see Figure 32). This bracket performs two
functions: supporting the heater from above, and intake and outlet of combustion products. It is supplied
complete with an external dual wind-protected terminal.
-
Adjustable lower mounting bracket. This supports the heater from below and allows it to adjusted by
±
30°
in relation to the wall used for installation; it is supplied complete with condensate drain and air/exhaust gas
pipe connection kit with elements for drawing air/exhaust gas (see Figure 33).
- tubular support bracket. This supports the heater from below, and is supplied complete condensate drain
and air/exhaust gas pipe connection kit with elements for drawing air/exhaust gas (see Figure 34).
If it is not intended to use these accessories, refer to the diagram below. As regards fixing the appliance to the
support shelf, fix the latter with 4 M10 bolts.
Figure 14
1 = EXHAUST GAS OUTLET
2 = COMBUSTION AIR INTAKE
290
FRONT VIEW
POSITION
RECOMMENDED
2
1
POSITION
ALLOWED
2
1
POSITION NOT
ALLOWED
2
1
25
790
400