Diagnostics
Installation, use and maintenance manual – AY
43
8
12
Flame controller lockout
NA
Check gas supply.
The reset can be carried out from DDC or from the boiler
panel by pressing the
key.
If the code persists or in case of doubt, contact the TAC.
31
No CAN bus communication
Contact authorised Technical Assistance
NA
36
Blower fault
Reset occurs automatically 20 minutes
after the code is generated.
The reset can be carried out from DDC or from the boiler
panel by pressing the
key.
If the code persists, shows up again or in case of doubt,
contact the TAC.
41
Flame controller error
NA
The reset can be carried out from DDC or from the boiler
panel by pressing the
key.
If the code persists, shows up again or in case of doubt,
contact the TAC.
73
Insufficient water pressure
Reset is automatic when the triggering
condition ceases.
NA
74
AUX temperature probe fault
Reset is automatic when the triggering
condition ceases.
NA
75
Low hot water flow
Reset is automatic when the triggering
condition ceases.
Check and clean water filters on the system.
Check for air in the system.
Check water flow pump.
Power cycle the appliance.
The reset can be carried out from DDC or from the boiler
panel by pressing the
key.
If the code persists, shows up again or in case of doubt,
contact the TAC.
76
Hot water delivery temperature
probe fault
Reset is automatic when the triggering
condition ceases.
NA
77
Hot water inlet temperature
probe fault
Reset is automatic when the triggering
condition ceases.
NA
83
Invalid functional parameters
NA
Power off the appliance.
Contact the TAC.
84
Incorrect supply voltage
Reset is automatic when the triggering
condition ceases.
NA
86
Internal boiler board error
NA
Power off the appliance.
Contact the TAC.
87
No communication with
CAN-NDG board
Reset is automatic if communication is
restored within 60 seconds. Otherwise, a
reset of the CAN-NDG board is forced and
W182 is raised.
Contact the TAC.
90
Outdoor temperature probe fault
Reset is automatic when the triggering
condition ceases.
NA
NA: Not Applicable
Error codes generated by the CAN-NDG board (displayed only on the DDC
control, if any)
Code
Description
Warning (u)
Error (E)
180
Incomplete functional parameters
Contact the TAC.
181
Error in storing configuration parameters
on CAN-NDG board
Reset is automatic when the triggering
condition ceases.
Contact the TAC.
182
CAN-NDG board reset
Reset is automatic when the triggering
condition ceases.
NA
185
Invalid module type configuration param-
eters
NA
Contact the TAC.
188
Boiler parameters reading error
Reset is automatic the next time the
parameters are read correctly.
NA
189
Boiler parameters writing error
NA
Run parameter writing again.
192
Incompatibility of boiler board FW version NA
Contact the TAC.
NA: Not Applicable
The special functions listed below are also shown on the
DDC control, if any, as warnings, always adding the hun-
dreds digit "1" to the code.