First start-up
34
5
P52
Glycol percentage
It is possible to set the percentage of glycol in the system water.
0 ÷ 60
0
Value in percentage
P54
Heating run-up
It is possible to set the time, during the start-up phase, that the boiler takes
to reach the maximum set power (for the space heating service).
0 ÷ 4
1
0. disabled
1. 50 s
2. 100 s
3. 200 s
4. 300 s
P58
Post-circulation heating timing
It is possible to set the operating time of the pump, in heating mode, after
the main burner has been switched off due to the intervention of the room
thermostat.
0 ÷ 90
36
Value in multiples of 5 s
(default 36 x 5 = 180 s)
P62
Minimum blower speed adjustment for heating
It is possible to set the minimum speed of the blower for the heating
service, which corresponds to the minimum power of the burner during a
heating request (see Figure 5.5
p. 36). The value is preset according to the
boiler model (P10) and the Mod1 type (P30).
33 ÷ min
between 133
and P63
53
Value in hertz (1 Hz = 30 RPM)
P63
Maximum blower speed adjustment for heating
It is possible to set the maximum speed of the blower for the heating
service, which corresponds to the maximum power of the burner during a
heating request (see Figure 5.5
p. 36). The value is preset according to the
boiler model (P10) and the Mod1 type (P30).
maximum
between 40
and P62 ÷
290
247
Value in hertz (1 Hz = 30 RPM)
P64
Starting step adjustment
It is possible to set the blower speed during the start-up phases. The value is
preset according to the boiler model (P10) and the Mod1 type (P30).
33 ÷ 255
130
Value in hertz (1 Hz = 30 RPM)
P66 (1) (2)
Setting the climatic curve
The appliance is equipped with an outdoor temperature probe (located
onboard the appliance) that acts by automatically changing the outlet tem-
perature according to the measured outdoor temperature. The extent of the
correction depends on the set heating control value Kd (Figure 5.3
The choice of the curve is determined by the maximum outlet temperature
Tm and the minimum outdoor temperature Te, taking into account the
degree of insulation of the building. The values of the outlet temperatures
Tm refer to standard systems 30÷80 °C.
0
1 ÷ 30
0
0. disabled
The numbering of the value
corresponds to the 'Kd'
curves of the graph (Figure
5.3
P68 (1) (3)
0-10 V industrial bus drive enable
The 0-10 V industrial bus input can be enabled or disabled to set burner
power or delivery temperature via the external bus.
0 ÷ 2
0
0. disabled
1. temperature control mode
2. power control mode
P69
Min heating setpoint
It is possible to set the minimum user-adjustable heating temperature.
20 ÷ 40
30
Value in °C
P70
Max heating setpoint
It is possible to set the maximum user-adjustable heating temperature.
40 ÷ 88
80
Value in °C
P72
Δt delivery-return setpoint
It is possible to set the temperature difference between delivery and return.
0
5 ÷ 40
20
0. disabled
Value in °C
P73
Modulating pump minimum speed
50 ÷ 70
60
Do not change
P74
Modulating pump maximum speed
70 ÷ 100
100
Do not change
P78
Control mode
It is possible to set the control mode of the boiler.
0 ÷ 2
0
0. CAN bus
1. do not use
2. external request
P81
Heating antifreeze temperature setting
It is possible to set the temperature of the water in the heating system at
which the antifreeze protection is activated.
5 ÷ 12
12
Value in °C
P82
Flowmeter type
0 ÷ 2
2
Do not change
P83
Minimum water flow setting
20 ÷ 68
30
Do not change
1. The climatic curve and the use of the 0-10 V input are
alternative functions. If both functions are configured
as active, the climatic curve is used. These functions
are only used in the case of control via external re-
quest (P78 = 2).
2. With the climatic curve active, the outlet water setpoint
temperature is set to a value between that of param-
eters P69 and P70 based on the outdoor temperature
measured by the probe inside the appliance and on
the Kd value set in parameter P66 (Figure 5.3
3. With 0-10 V input active in temperature control mode,
the outlet water setpoint is set to a value between that
of parameters P69 and P70 based on the line passing
through the points (3 V, P69) and (10 V, P70). A volt-
age lower than 3 V corresponds to no service request.
With 0-10 V input active in power control mode, the
thermal output is set to a value between the minimum
and maximum power according to the line passing
through the points (3 V, minimum power) and (10
V, maximum power). A voltage lower than 3 V corre-
sponds to no service request. Control via 0-10 V input
is not available for AY 100.