Settings
Display Adjustment Options
Default
Minimum
Compressor
On-Time
The installer can select the
minimum run time for the
compressor to help protect the
compressor from short-cycling.
The minimum compressor run time
can be adjusted from
OFF
to 3, 4, or
5 minutes. If 3, 4, or 5 is selected,
the compressor will run for at least
the selected time before turning off
(although the fan may continue to
run for a short time).
OFF
Compressor
Short Cycle
Delay
The compressor short cycle delay
setting will not allow the compres-
sor to be turned on for 5 minutes
after it was last turned off in order
to protect the compressor.
The compressor short cycle
delay setting can be removed by
selecting
OFF.
ON
Cooling
Differential
The cooling differential is factory
preset at 0.5°. This means that
whenever the room temperature
heats by 0.5° full degree from the
temperature setting, the cooling
system will turn on. If the cooling
system turns on too often, increase
the temperature differential.
The cooling differential setting is
adjustable from 0.2°F to 2°F.
0.5