Rhein - Nadel Automation GmbH 

                     4 

                                                         14.04.2014 

VT-BA Typ ESG 1000 GB 

 

Safety notes 

 
The  safety  notes  shall  in  any  case  be  read  and  understood.  Their  observance  secures  the  conservation  of  valuable 
material and avoids health impairment. 
 
 
                 

 

 
 

 

The symbol of the pointing hand is shown in these operating instructions at points, which must be 
particularly  observed,  so  that  recommendations,  regulations,  notes  and  the  correct  procedure  of 
work can be observed, as well as damage and destruction of the machine and/or other equipment 
parts is avoided. 

 
 
 

 

 

Electric danger, 

eg. at work under voltage

 

 
 
 
 
 
 
 

 

Work at electrical equipment of the machine/equipment may only be carried out by a qualified electrician 
or  by  trained  personnel  under  direction  and  supervision  of  a  qualified  electrician according to the elec-
tronic regulations! 
 
All safety and danger notes at the machine / equipment must be observed!! 
 
The electrical equipment of a machine / equipment must be examined regularly. Faults, eg. loose con-
nections or damaged cables, must be eliminated immediately! 

 
 
 

 

 
Before opening the device unplug the power plug! 

 

Information for starting. 

 
 

Before the mains connection is made and the control unit is switched on, the following points must in any 
case be checked: 

  Is the control unit closed properly and with all screws? 

  Are the existing plug fixing devices locked into place/screwed down? 

  Are all cables and ducts undamaged? 

  Is the 

INTENDED USE

 guaranteed? 

  Does the mains voltage indication comply with the local power supply network? 

  Does the mains frequency indication at the oscillating drive comply with the local power supply net-

work? 

  Is the correct operating mode set at the control unit?  (on that read explanation operating mode) 

 
Only if all above mentioned questions can be answered with yes, the control unit can be put into operation. 
 
 

At initial starts or starts after repair work or exchange of control units/oscillating drives the minimum output 
should be set at the control unit before switching on the device. When bringing up the output it must be tak-
en care for correct function. 

 

3.1 

Explanations on the term OPERATING MODE 

 
RNA - Oscillating drives are mechanical spring vibrators, which, according to weight and/or size, are adjusted to an os-
cillating frequency near the mains frequency. Two operating modes are possible:  
   1. Asymmetrical half-wave operation - the oscillating  
       drive operates with mains frequency. 
   2. Symmetrical full-wave operation - the oscillating 
      drive operates with double mains frequency. 
 
 
 
 
 
 

Summary of Contents for ESG 1000

Page 1: ...Rhein Nadel Automation GmbH 1 19 09 2012 VT BA Typ ESG 1000 GB Operating instructions Control units for oscillating drives ESG 1000 BA Rhein Nadel Automation GmbH...

Page 2: ...he boards 7 5 Dimensional drawing 8 6 Connection diagram 8 Declaration of conformity as defined by Low voltage directive 2014 35 EU and EMC directive 2014 30 EU Herewith we declare that the product co...

Page 3: ...approx 0 5 seconds If necessary this time can be changed in the device 1 2 EC Conformity The control device corresponds to the following regulations Low voltage directive 2014 35 EU EMC directive 2014...

Page 4: ...ade and the control unit is switched on the following points must in any case be checked Is the control unit closed properly and with all screws Are the existing plug fixing devices locked into place...

Page 5: ...ion 3 to 4 switches the control unit into operating mode 2 100 or 120 Hz If this connection is missing the control unit operates in the operating mode 1 50 or 60 Hz As a standard oscillating transport...

Page 6: ...witched on Should it be preferred that the control unit work in start stop operation then the control unit should be opened observing all of the precautionary measures listed above and the jumper S1 r...

Page 7: ...ignal is fed between 10 and 30 volt direct current in correct polarity The input is protected against faulty polarity The use of an optocoupler in the control unit makes the input potential free and a...

Page 8: ...Rhein Nadel Automation GmbH 8 14 04 2014 VT BA Typ ESG 1000 GB 5 Scale Drawing 6 Connecting Diagram...

Page 9: ...lding rna de PSA Zuf hrtechnik GmbH Dr Jakob Berlinger Weg 1 D 74523 Schw bisch Hall Tel 49 0 791 9460098 0 Fax 49 0 791 9460098 29 Email info psa zt de HSH Handling Systems AG Wangenstr 96 CH 3360 He...