background image

ISSUE 2016 Rev 1 - Installation Manual 

RM Cylinders 

 

Commissioning - filling the system 
 
Check all connections for water tightness including factory made connections such as the temperature and pressure relief valve, as these may 
have been loosened during transit.   
 
The hot tap furthest away from the cylinder should be opened before filling the system to purge air and flush any disturbed particles 
 
The system should be flushed before use. The remaining taps should be opened in turn to purge air from the system before turning on the 
electrical supply. 

 
For Direct Units

: The system must be fully filled and flushed before switching on the power to the immersion heaters and allowing the unit 

to heat up. The immersion heater is supplied pre-set at 60°C. Turning fully to + sets to approximately 65°C. 

 
For Indirect Units

: Ensure the lever on the two port valve is set to the filling position and use the boiler manufacturer’s commissioning 

instructions to fill the primary circuit. When full, release the lever. Switch the programmer to Domestic Hot Water (DHW) and allow the unit 
to start to heat. It is usual to set the thermostat to 60°C. 
 
Storage Temperature 
 
A storage temperature of 60°C is normal for both direct and indirect units. In hard water areas, consider reducing this to 55-60°C. 
 
Safety Valve Check 
 
If water is being released from either the expansion relief or the temperature and pressure relief valve during heat up, then this is indicative of 
a problem that needs rectifying. Both valves should be opened slowly one at a time, and then together, allowing as much water to flow 
through the tundish. Check that the discharge pipework is free from debris and the discharge can flow freely, without spillage over the 
tundish. Check that the valves reseat correctly when released. 
 
Draining the Cylinder 
 
Isolate from the electric supply to prevent the immersion heaters burning out. Isolate the unit from the cold mains. Attach a hose to the 
draining tap ensuring it reaches to a level below the unit, as this will ensure an efficient siphon is set up and the maximum amount of water is 
drained from the unit. Open the hot tap closest to the unit and open the draining tap. 

 
Note:

 Water drained off may be hot. 

 

SERVICE AND MAINTENANCE 

 

Servicing must be carried out annually and should only be carried out by competent installers. Any spare parts used must be purchased from 
RM Cylinders. Never bypass any safety devices or operate the unit without these being fully operational 
 
Your guarantee may be void without proof of annual servicing via the Service record within this manual. The installer upon installation of the 
unit must also complete the accompanying commissioning certificate. 
 
Annual Servicing Requirements 
 
A competent installer should carry out the following checks on an annual basis, ideally at the same time as the annual boiler service. 
 
1.

 

The expansion relief valve on the inlet control set should be eased open allowing water to flow for a minimum of 5 seconds. The 
valve should then be closed making sure it resets correctly. Repeat this procedure with the pressure/temperature relief valve. Insure 
that the discharge pipework is allowing the water to flow freely, and clear any blockages if this is not the case. 

2.

 

Ensure that all immersion heaters fitted are working correctly and are controlling the water temperature between 55°C and 60°C. 

3.

 

This cylinder has no external expansion vessel. Expansion of heated water is accommodated by an entrapment of air in the upper 
section of the cylinder separated by a composite disc interface which rises and falls as the stored water heats and cools. At an annual 
service, it is necessary to ensure the level of the disc is correct by the following steps. 

a)

 

Isolate the cold mains supply to the cylinder. 

b)

 

Turn on a hot tap outlet 

c)

 

Open the Temperature and Pressure Relief Valve until water stops flowing from both the Relief Valve and the hot tap. 

d)

 

Close both the Relief Valve and the hot tap. 

e)

 

Turn the incoming cold mains on and allow the cylinder to fill 

f)

 

Re-open the hot tap until water flows and then close 

g)

 

The correct level for the interface disc will then have been re-established. 

4.

 

Remove the head on the inlet control set by unscrewing it, and clean the mesh filter within 

5.

 

The benchmark service record supplied within this manual should be updated at each service. 

Summary of Contents for Intercyl

Page 1: ...INSTALLATION MANUAL Issue 2016 Rev 1 Tested to BS EN 12897 2006 FOR MORE INFORMATION GO TO WWW RMCYLINDERS COM Note By installing this product you agree to be bound by our Conditions of Sale found wi...

Page 2: ...2 Product Specifications 3 General Installation and Commissioning 6 Service and Maintenance 9 Fault Finding 10 Benchmark Commissioning Checklist 15 Service Record 16 User Guide and Customer Service 17...

Page 3: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders 2...

Page 4: ...responsibilities on both manufacturers and installers The purpose is to ensure that customers are provided with the correct equipment for their needs that it is installed commissioned and serviced in...

Page 5: ...a flat base capable of supporting the weight of the cylinder when full The minimum recommended cupboard size is 650mm square Nominal diameter of cylinder is 545mm Areas that are subject to freezing sh...

Page 6: ...0 15MPa 1 5 bar working pressure and a 20 litres per minute flow rate Where mains inlet pressures Hot Outlet Non Return Valve Pump Temperature and Pressure Relief Valve Secondary Return Boiler Flow B...

Page 7: ...n order to service the inlet control set Ensure the directional flow arrow on the inlet control set follows the required flow of water See schematic diagram A balanced cold supply is necessary if ther...

Page 8: ...ld utilise the dual control high limit thermostat as described in Connection to a Boiler section For connection to the lower coil you will require a further two port valve and a single control thermos...

Page 9: ...700 Specification for the design installation testing and maintenance of services supplying water for domestic use within buildings and their curtilages From the tundish pipework should terminate in a...

Page 10: ...of water is drained from the unit Open the hot tap closest to the unit and open the draining tap Note Water drained off may be hot SERVICE AND MAINTENANCE Servicing must be carried out annually and s...

Page 11: ...erating tap outlet Insecure Pipework Increase the number of pipe clips External works to public mains Wait for works to be completed Reduced water flow Debris from water mains Strip cleanorreplace Inl...

Page 12: ...DING Is water running from the Tundish Is the water being discharged hot Tundish YES NO Do you have pressure YES NO No fault See the flow chart for T P Valve See the flow chart for Inlet Control Group...

Page 13: ...mperature Pressure Relief Valve YES NO Do you have pressure YES NO No fault with the T P No fault with the T P Replace T P if required Replace T P if required Check temperature setting of the cylinder...

Page 14: ...st fails replace Dual Stat Test Stat continuity Reset Limit Stat Test Dual Stat continuity Is there power to the Element Thermostat Has the thermostat tripped Does the Immersion Heater work Find corre...

Page 15: ...RM Cylinders ENERGY CUT OUT FAULT FINDING Is the Cut Out Thermostat working Test Stat continuity Energy Cut Out Thermostat NO YES Reset Limit Stat No fault with the Thermostat If test fails replace Du...

Page 16: ...incoming static cold water pressure at the inlet to the system Has a strainer been cleaned of installation debris if fitted Is the installation in a hard water area above 200ppm If yes has a water sca...

Page 17: ...VICE 9 Date Engineer Name Company Name Telephone Number Signature SERVICE 8 Date Engineer Name Company Name Telephone Number Signature SERVICE 7 Date Engineer Name Company Name Telephone Number Signat...

Page 18: ...uty installations where constant usage and reheating is required titanium immersion heaters must be fitted to comply with the warranty Exclusions 16 The effect of scale build up on the unit or its com...

Page 19: ...1 Installation Manual 3 RM Cylinders TYPICAL WIRING S PLAN 1 ZONE TYPICAL WIRING Y PLAN COLOUR CODES W WHITE G GREY BL BLUE G Y GREEN YELLOW L LIVE N NEUTRAL C COMMON SL SWITCHED LIVE E EARTH 3 Port M...

Page 20: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders TYPICAL WIRING S PLAN 2 ZONE COLOUR CODES W WHITE G GREY BL BLUE G Y GREEN YELLOW L LIVE N NEUTRAL C COMMON SL SWITCHED LIVE E EARTH 19...

Page 21: ...ll the goods to third parties in the normal course of business In this respect the Buyer shall act in the capacity of the Companies commission agent and the proceeds of such sale 6 6 1 shall be held i...

Page 22: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders NOTES 21...

Reviews: