RM Cylinders Intercyl Installation Manual Download Page 7

ISSUE 2016 Rev 1 - Installation Manual 

RM Cylinders 

 

may exceed 10 bar, then an additional upstream pressure reducing device should be fitted. 
 
The mains supply pipe-work should be a minimum of 22mm, which may entail upgrading the existing 1/2” (15mm) cold mains pipe-work. 
 
The water supply must be of a wholesome water quality, defined as Fluid Category 1 in the Water Supply Regulations 1999. In areas of hard 
water content greater than 200ppm, treatment for this should be installed. 
 
Electric Supply 
 
This appliance must be earthed. It is suitable for a 240 volt A.C. supply only. The electrical installation must be carried out by a competent 
electrician and be in accordance with the latest I.E.E. wiring regulations. 
Ensure the electrical supply is isolated before making any connections to the cylinder. 
 

GENERAL INSTALLATION AND COMMISSIONING

 

 
Cylinder Connections 
 
The standard pipework connections on the cylinder are 22.0mm compression. 
 
Should imperial ¾” tube be used then imperial ¾” olives are required for successful connection to the cylinder. 
 
Cold Mains Pipework 
 
The cold mains pipework should be a minimum of 22mm, through to the cylinder installation. Care should be taken not to run cold water 
pipes adjacent to hot water or heating pipework, thus minimising any heat transfer. Install an isolating valve (not supplied) to the cold mains 
pipework. Typically, a 22mm BS1010 stopcock or a quarter turn full-bore lever valve should be used, do not use a screwdriver slot, or other 
similar valves. 
 
Make the connection to the cold feed of the cylinder, incorporating a drain valve.  
 
Inlet Control Set  
 
The inlet control set comprises of a 3.0bar pressure reducing valve, 8.0bar expansion relief valve, non return valve, in-line strainer, 22mm 
compression connections for cold entry, outlet to the cylinder and an outlet for a balanced cold supply. The inlet control must be positioned 
above the Temperature and Pressure Relief Valve (TPRV) that is mounted on the side of the cylinder. This position ensures the cylinder does 
not have to be drained in order to service the inlet control set. Ensure the directional flow arrow on the inlet control set follows the required 
flow of water. 

See schematic diagram.

 

 
A balanced cold supply is necessary if there are to be any showers, bidets, or monobloc taps in the installation. Connection to the balanced 
cold outlet will facilitate this requirement ensuring both hot and cold outlets are automatically balanced upon filling.  
 
Expansion of Heated Water 
 
The expansion of heated water in the cylinder is accommodated by an entrapment of air in the upper section of the cylinder. This is separated 
by a composite disc interface which rises and falls as the stored water heats and cools. The required levels of water and air are established 
automatically upon filling and require no specific commissioning. Servicing is required - 

see service section 

 
In usage there may be occasions when heated hot water pressure may rise to approaching 8.0bar which may affect some terminal fittings. To 
overcome this, consideration should be given to installing a 3.0bar pressure control valve 

(available from RM Cylinders)

, to the hot outlet 

pipework of the system.  
 
Hot Water Pipework 
 
The main section of hot water distribution pipework should be installed in 22mm, which can be reduced to 15mm and 10mm dependent on the 
type of tap. The volume of the hot draw off pipework should be kept to a minimum so the transfer of the hot water to outlets is as quick as 
possible. Do not use monobloc mixer taps or showers if the balanced cold connection is not provided, as the unit will back pressurise and 
result in discharge. Ensure that the top of the vessel is accessible for servicing. 
 
Secondary Circulation 
 
Where secondary circulation is required a potable water circulator should be used in conjunction with a non-return check valve to prevent any 
backflow. Larger secondary circulation systems may require an external expansion vessel should the increased expansion requirement be 
greater than can be accommodated within the cylinder. A bespoke secondary return connection is supplied on 210, 250, 300 single coil 
indirect and twin coil indirect models. On smaller sizes, the return can be introduced into the cold feed pipe between the inlet control set and 

Summary of Contents for Intercyl

Page 1: ...INSTALLATION MANUAL Issue 2016 Rev 1 Tested to BS EN 12897 2006 FOR MORE INFORMATION GO TO WWW RMCYLINDERS COM Note By installing this product you agree to be bound by our Conditions of Sale found wi...

Page 2: ...2 Product Specifications 3 General Installation and Commissioning 6 Service and Maintenance 9 Fault Finding 10 Benchmark Commissioning Checklist 15 Service Record 16 User Guide and Customer Service 17...

Page 3: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders 2...

Page 4: ...responsibilities on both manufacturers and installers The purpose is to ensure that customers are provided with the correct equipment for their needs that it is installed commissioned and serviced in...

Page 5: ...a flat base capable of supporting the weight of the cylinder when full The minimum recommended cupboard size is 650mm square Nominal diameter of cylinder is 545mm Areas that are subject to freezing sh...

Page 6: ...0 15MPa 1 5 bar working pressure and a 20 litres per minute flow rate Where mains inlet pressures Hot Outlet Non Return Valve Pump Temperature and Pressure Relief Valve Secondary Return Boiler Flow B...

Page 7: ...n order to service the inlet control set Ensure the directional flow arrow on the inlet control set follows the required flow of water See schematic diagram A balanced cold supply is necessary if ther...

Page 8: ...ld utilise the dual control high limit thermostat as described in Connection to a Boiler section For connection to the lower coil you will require a further two port valve and a single control thermos...

Page 9: ...700 Specification for the design installation testing and maintenance of services supplying water for domestic use within buildings and their curtilages From the tundish pipework should terminate in a...

Page 10: ...of water is drained from the unit Open the hot tap closest to the unit and open the draining tap Note Water drained off may be hot SERVICE AND MAINTENANCE Servicing must be carried out annually and s...

Page 11: ...erating tap outlet Insecure Pipework Increase the number of pipe clips External works to public mains Wait for works to be completed Reduced water flow Debris from water mains Strip cleanorreplace Inl...

Page 12: ...DING Is water running from the Tundish Is the water being discharged hot Tundish YES NO Do you have pressure YES NO No fault See the flow chart for T P Valve See the flow chart for Inlet Control Group...

Page 13: ...mperature Pressure Relief Valve YES NO Do you have pressure YES NO No fault with the T P No fault with the T P Replace T P if required Replace T P if required Check temperature setting of the cylinder...

Page 14: ...st fails replace Dual Stat Test Stat continuity Reset Limit Stat Test Dual Stat continuity Is there power to the Element Thermostat Has the thermostat tripped Does the Immersion Heater work Find corre...

Page 15: ...RM Cylinders ENERGY CUT OUT FAULT FINDING Is the Cut Out Thermostat working Test Stat continuity Energy Cut Out Thermostat NO YES Reset Limit Stat No fault with the Thermostat If test fails replace Du...

Page 16: ...incoming static cold water pressure at the inlet to the system Has a strainer been cleaned of installation debris if fitted Is the installation in a hard water area above 200ppm If yes has a water sca...

Page 17: ...VICE 9 Date Engineer Name Company Name Telephone Number Signature SERVICE 8 Date Engineer Name Company Name Telephone Number Signature SERVICE 7 Date Engineer Name Company Name Telephone Number Signat...

Page 18: ...uty installations where constant usage and reheating is required titanium immersion heaters must be fitted to comply with the warranty Exclusions 16 The effect of scale build up on the unit or its com...

Page 19: ...1 Installation Manual 3 RM Cylinders TYPICAL WIRING S PLAN 1 ZONE TYPICAL WIRING Y PLAN COLOUR CODES W WHITE G GREY BL BLUE G Y GREEN YELLOW L LIVE N NEUTRAL C COMMON SL SWITCHED LIVE E EARTH 3 Port M...

Page 20: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders TYPICAL WIRING S PLAN 2 ZONE COLOUR CODES W WHITE G GREY BL BLUE G Y GREEN YELLOW L LIVE N NEUTRAL C COMMON SL SWITCHED LIVE E EARTH 19...

Page 21: ...ll the goods to third parties in the normal course of business In this respect the Buyer shall act in the capacity of the Companies commission agent and the proceeds of such sale 6 6 1 shall be held i...

Page 22: ...ISSUE 2016 Rev 1 Installation Manual 3 RM Cylinders NOTES 21...

Reviews: