RKC INSTRUMENT V-TIO-E Instruction Manual Download Page 9

 

IMS01P04-E4

 

9

• 

Terminal No. 11 is not used. 

• 

Use the solderless terminal appropriate to the screw 
size (M3)

.

 

 
 
 

 
6.3 Pin Layout of Connector 

 

Modular connector 

 

Modular connector 

6

 

1

 

COM. PORT1

COM. PORT2

COM. PORT3

 

 

Modular connector

 COM. PORT1: 

Connector for PLC or Host computer connection 
Based on RS-422A/RS-232C (Specify when ordering) 

Modular connector

 COM. PORT2: 

Connector for PLC or Host computer connection 
Based on RS-422A 

Modular connector

 COM. PORT3: 

Connector for SRV unit extension 
Based on RS-422A 

 

 

RS-422A 

Pin No. 

Signal name 

Symbol 

Receive data 

R (A) 

Receive data 

R (B) 

3 Signal 

ground  SG 

Send data 

T (B) 

Send data 

T (A) 

6 Signal 

ground  SG 

 

 

RS-232C 

Pin No. 

Signal name 

Symbol 

1 Unused 

 

Send data 

SD (TXD) 

3 Signal 

ground  SG 

Receive data 

RD (RXD) 

5 Unused 

 

6 Signal 

ground  SG 

 

Customer is requested to prepare a communication 
cable fit for the V-TIO-E/F module to be connected by 
the host computer or PLC. 
Connection cable W-BF-01*, W-BF-02* and W-BF-28 
(RKC product) can use to connect the host computer or 
PLC. 

* Shields of the cable are connected to SG (No. 6 pin) of 

the X-TIO-E/F connector. 

 

The six-pin type modular connector should be used for 
the connection to the V-TIO-E/F module. 
Recommended manufacturer and model:   

Hirose Electric, TM4P-66P 

 

Event input/output connector 

 

1

6

Event input/output 

connector (socket) 

 

 

 

Circuit configuration 

 

24 V DC

1

2

3

DI 

4

5

6

Load

DO1

DO2

Load

 

 

 

Attention in Connector (plug) Wiring 

• 

Use the following connector (plug) as that connected to the 
event input/output connector.   
Connector (plug) is sold separately. 
SRVP-01 (Front-screw type) 
SRVP-02 (Side-screw type) 

• 

The lead wires use the stranded wire. 

• 

Use the stranded wire from size 0.2 to 2.5 mm

2

 (AWG 24-12). 

• 

Stripping length is as follows.

 

SRVP-01: 10 mm 
SRVP-02: 7 mm 

• 

Recommended tightening torque of the lead wire in the 
connector (plug):  0.5 to 0.6 N

m (5 to 6 kgf

cm) 

Screw size:  SRVP-01:  M2.5 
 SRVP-01: 

M3 

 

[SRVP-01] Front-screw type 

[SRVP-02] Side-screw type

Stripping length

10 mm 

Stranded wire size: 
 0.2 

to 

2.5 

mm

 (AWG 

24-12) 

Recommended tightening 
torque:  0.5 to 0.6 N

 

(5 to 6 kgf

cm) 

Stripping length

7 mm 

Stranded wire size: 
 

0.2 to 2.5 mm

 (AWG 

24-12) 

Recommended tightening 
torque:  0.5 to 0.6 N

 

(5 to 6 kgf

cm) 

 

 

 

5.9 mm or less

3.2 mm or more 

Recommended tightening 
torque:

 0.4 N

m (4 kgf

cm)

 

Pin 
No. 

Description 

Digital input (DI)  (

Digital input (DI)  (

+


Digital output (DO) 1 
(Relay contact output) 


Digital output (DO) 2 
(Relay contact output) 

 

 

Summary of Contents for V-TIO-E

Page 1: ...osed instrumentation panel All high voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions desc...

Page 2: ...groups and then installed Usable modules Temperature control TIO module Basic type V TIO A C Temperature control TIO module Extension type V TIO B D Up to 30 modules Event input output connector optio...

Page 3: ...JPt100 P17 0 to 400 C PC5 32 to 752 F P23 0 to 600 C PC4 32 to 1112 F P16 0 0 to 400 0 C PC7 32 0 to 752 0 F P28 200 0 to 400 0 C PC6 328 0 to 752 0 F Voltage current input Code Type Code Type Voltage...

Page 4: ...e See P 5 Set the unit address for PLC communication PLC communication setting switch left side See P 5 Set the communication speed data bit configuration and protocol for PLC communication Set the sa...

Page 5: ...imal Factory set value 0 9 8 7 C B A 6 543 2 1 0 F E D Address setting switch 2 for unit address PLC communication Up to four V TIO E F modules can be connected to a PLC communication port Therefore t...

Page 6: ...ps ON ON 38400 bps Factory set value 9600 bps 3 4 5 Data bit configuration OFF OFF OFF Data 7 bit without parity Stop 1 bit OFF OFF ON Data 7 bit Even parity Stop 1 bit OFF ON OFF Don t set this one O...

Page 7: ...y reach of the operator It shall be marked as the disconnecting device for the equipment 5 2 Dimensions Unit mm 110 6 8 40 5 125 78 5 The above figure shows when provided with the event input output c...

Page 8: ...se induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could aff...

Page 9: ...e modular connector should be used for the connection to the V TIO E F module Recommended manufacturer and model Hirose Electric TM4P 66P Event input output connector 1 6 Event input output connector...

Page 10: ...low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Option Event input Number of inputs 1 point Input type Dry contact...

Reviews: