RKC INSTRUMENT V-TIO-E Instruction Manual Download Page 3

 

IMS01P04-E4

 

3

2. PRODUCT CHECK 

Before using this product, check each of the following: 

• 

Model code 

• 

Check that all of the accessories delivered are complete. 

• 

Check that there are no scratch or breakage in external 
appearance (case, front panel, or terminal, etc). 

V–TIO–     

 –     

     –     –  –   /Y 

(1) (2)  (3) 

(4)  (5)  (6) (7) (8)  (9) (10)  (11) (12) 

(1) Type 

E:  Module for PLC communication, heat control 
F:  Module for PLC communication, heat/cool control 

(2) Control action 

(Each channel common code)

 

[For heat control]

 

F:  PID action with autotuning (AT) (reverse action) 
D:  PID action with autotuning (AT) (direct action) 
[For heat/cool control] 
B:  Heat/cool PID action with autotuning (AT) (air cooling) 
W: Heat/cool PID action with autotuning (AT) (water cooling) 

(3) Input range 

(Each channel common code)

 

[Thermocouple input] 

Type 

Code Range  Code Range 

K02 

0 to 400 

°

KB9 

32 to 752 

°

 

K04 

0 to 800 

°

KB8 

32 to 1472 

°

 K16 

200 to 

+

1372 

°

C

KB7 

328 to 

+

2501 

°

F

 

K09 

0.0 to 400.0 

°

C

KC2 

32.0 to 752.0 

°

F

 K35 

200.0 to 

+

400.0 

°

C KC1 

328.0 to 

+

752.0 

°

F

J02 

0 to 400 

°

JC2 

32 to 752 

°

 

J04 

0 to 800 

°

JC1 

32 to 1472 

°

 J15 

200 to 

+

1200 

°

C

JB9 

328 to 

+

2192 

°

F

 

J09 

0.0 to 400.0 

°

C

JC4 

32.0 to 752.0 

°

F

 J27 

200.0 to 

+

400.0 

°

C JC3 

328.0 to 

+

752.0 

°

F

T08 

0 to 400 

°

TB9 

32 to 752 

°

 

T09 

0 to 200 

°

TC1 

32 to 392 

°

 T16 

200 to 

+

400 

°

C TB8 

328 to 

+

752 

°

 

T06 

0.0 to 400.0 

°

C

TC3 

32.0 to 752.0 

°

F

 T19 

200.0 to 

+

400.0 

°

C TC2 

328.0 to 

+

752.0 

°

F

E01 

0 to 800 

°

EA8 

32 to 1472 

°

 

E02 

0 to 1000 

°

EA7 

32 to 1832 

°

S05 

0 to 1768 

°

SA6 

32 to 3214 

°

R06 

0 to 1768 

°

RA6 

32 to 3214 

°

N02 

0 to 1300 

°

NA6 

32 to 2372 

°

B03 

0 to 1800 

°

BB1 

32 to 3272 

°

PL

 

A02 

0 to 1390 

°

AA6 

32 to 2534 

°

W5Re/ 
W26Re 

W03 

0 to 2300 

°

WA9 

32 to 4172 

°

[RTD input] 

Type 

Code Range  Code Range 

Pt100 

D17 

0 to 400 

°

DC5 

32 to 752 

°

 

D33 

0 to 850 

°

DC4 

32 to 1562 

°

 

D16 

0.0 to 400.0 

°

C

DC7 

32.0 to 752.0 

°

F

 D28 

200.0 to 

+

400.0 

°

C DC6 

328.0 to 

+

752.0 

°

F

JPt100 

P17 

0 to 400 

°

PC5 

32 to 752 

°

 

P23 

0 to 600 

°

PC4 

32 to 1112 

°

 

P16 

0.0 to 400.0 

°

C

PC7 

32.0 to 752.0 

°

F

 P28 

200.0 to 

+

400.0 

°

C PC6 

328.0 to 

+

752.0 

°

F

[Voltage/current input] 

 Code Type 

Code Type 

Voltage  201 

0 to 100 mV DC 

401 

0 to 5 V DC 

 

501 

0 to 10 V DC 

601 

1 to 5 V DC 

Current 

701 

0 to 20 mA DC 

801 

4 to 20 mA DC 

(4) Control output (CH1),  (5) Control output (CH2) 

M: Relay contact output 
V:  Voltage pulse output 0/12 V DC 
4:  0 to 5 V DC 

 

5:  0 to 10 V DC 

 

6:  1 to 5 V DC 
7:  0 to 20 mA DC 

 

8:  4 to 20 mA DC 

(6) Event input (DI)    [Optional] 

N: None 
1: Control RUN/STOP 
2:  Event interlock release

 

(7) (8)  Event output 1 (DO1)    [Optional]

 

1

 

(9) (10) Event output 2 (DO2)    [Optional]

 

1

 

[(7), (9) code: Channel selection] 
N: None 

 

1:  Input channel 1   
2:  Input channel 2 
[(8), (10) code: Output type] 
N: None 

 

A: Deviation high 

 

B: Deviation low 
C: Deviation high/low  

 

D: Band 
E: Deviation high with hold action   
F: Deviation low with hold action 
G: Deviation high/low with hold action 
H: Process high 

 

 

J: Process low 
K: Process high with hold action 

 

L:  Process low with hold action 
Q: Deviation high with re-hold action 

 

R: Deviation low with re-hold action 
T: Deviation high/low with re-hold action 
P: Heater break alarm 

 

 

1:  Control loop break alarm 
2: Burnout 

 

 

3:  Temperature rise completion 

(11) CT type 

(Each channel common code)

 

P: CTL-6-P-N 

 

S: CTL-12-S56-10L-N 

(12) Communication function (COM. PORT1) 

2

 

1: RS-232C 

 

4: RS-422A 

1

  When “N” is selected in (7) or (9), (8) or (10) becomes “N.” 

2

  Internal communication terminals is RS-485, COM. PORT2/ COM. 

PORT3 is RS-422A (Fixed). 

 

• 

For heat/cool PID control (V-TIO-F), input channel 
2 becomes unused. 

• 

For heat/cool PID control (V-TIO-F), Control output 
(CH1) corresponds to the heating output and 
Control output (CH2) corresponds to the cooling 
output. 

• 

The heater break alarm function becomes invalid 
when the voltage/current output is selected as 
control output type. 

 
 
 
 
 
 
 

 

If any of the products are missing, damaged, or if your 
manual is incomplete, please contact RKC sales office 
or the agent.

 

 

 

Accessories

 

End Plate.................................................................... 2 
Joint connector cover ................................................. 2 
Instruction Manual (IMS01P04-E4)............................ 1 

*

Summary of Contents for V-TIO-E

Page 1: ...osed instrumentation panel All high voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions desc...

Page 2: ...groups and then installed Usable modules Temperature control TIO module Basic type V TIO A C Temperature control TIO module Extension type V TIO B D Up to 30 modules Event input output connector optio...

Page 3: ...JPt100 P17 0 to 400 C PC5 32 to 752 F P23 0 to 600 C PC4 32 to 1112 F P16 0 0 to 400 0 C PC7 32 0 to 752 0 F P28 200 0 to 400 0 C PC6 328 0 to 752 0 F Voltage current input Code Type Code Type Voltage...

Page 4: ...e See P 5 Set the unit address for PLC communication PLC communication setting switch left side See P 5 Set the communication speed data bit configuration and protocol for PLC communication Set the sa...

Page 5: ...imal Factory set value 0 9 8 7 C B A 6 543 2 1 0 F E D Address setting switch 2 for unit address PLC communication Up to four V TIO E F modules can be connected to a PLC communication port Therefore t...

Page 6: ...ps ON ON 38400 bps Factory set value 9600 bps 3 4 5 Data bit configuration OFF OFF OFF Data 7 bit without parity Stop 1 bit OFF OFF ON Data 7 bit Even parity Stop 1 bit OFF ON OFF Don t set this one O...

Page 7: ...y reach of the operator It shall be marked as the disconnecting device for the equipment 5 2 Dimensions Unit mm 110 6 8 40 5 125 78 5 The above figure shows when provided with the event input output c...

Page 8: ...se induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could aff...

Page 9: ...e modular connector should be used for the connection to the V TIO E F module Recommended manufacturer and model Hirose Electric TM4P 66P Event input output connector 1 6 Event input output connector...

Page 10: ...low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Option Event input Number of inputs 1 point Input type Dry contact...