RKC INSTRUMENT V-TIO-E Instruction Manual Download Page 7

 

IMS01P04-E4

 

7

5. MOUNTING 

 
 
 
 
 
 

 

5.1 Mounting Cautions 

(1) This instrument is intended to be used under the following 

environmental conditions. 

(IEC61010-1)

   

[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]

 

(2)  Use this instrument within the following environment conditions. 

• 

Allowable ambient temperature: 

10 to 

+

50 

°

• 

Allowable ambient humidity: 5 to 95 % RH 
(Absolute humidity: MAX.W.C 29.3 g/m

3

 dry air at 101.3 kPa) 

• 

Installation environment conditions:  Indoor use   
 

Altitude up to 2000 m 

(3)  Avoid the following when selecting the mounting location.

 

• 

Rapid changes in ambient temperature, which may cause 
condensation. 

• 

Corrosive or inflammable gases. 

• 

Direct vibration or shock to the mainframe. 

• 

Water, oil, chemicals, vapor or steam splashes. 

• 

Excessive dust, salt or iron particles. 

• 

Excessive induction noise, static electricity, magnetic fields or 
noise. 

• 

Direct air flow from an air conditioner. 

• 

Exposure to direct sunlight. 

• 

Excessive heat accumulation. 

(4) Mounting consideration  

• 

Install the module 200 mm away from the main power line. 

• 

Ensure at least 50 mm space on top and bottom of the control 
unit for maintenance and environmental reasons. 

(5) 

This instrument is permanently connected to equipment, 
please take the following points. 

• 

A switch or circuit-breaker shall be included in the building 
installation. 

• 

It shall be in close proximity to the equipment and within easy 
reach of the operator. 

• 

It shall be marked as the disconnecting device for the 
equipment. 

 

5.2 Dimensions 

(Unit: mm) 

 

110

 

6.8

 

40.5

125

 

78

 

5

 

 

The above figure shows when provided with the event 

input/output connector, but the same also when not 

provided with the connector. 

 

 

Depth in connector mounting

 

Conduct installation in consideration of the sizes of the 

connector and cable when connector-connected. 

 

110

[Usage example of SRVP-01]

 

(Unit: mm)

Approx. 50

 

Connector (plug):
SRVP-01  
(sold separately) 

 

 

5.3 DIN rail Mounting 

 

Mounting procedures 

1. 

Pull down the mounting bracket at the bottom of the module 
(A). Attach the hooks on the top of the module to the DIN rail 
and push the lower section into place on the DIN rail (B).   
(Fig. 1) 

2. 

Slide the mounting bracket up to secure the module to the 
DIN rail. (Fig. 2) 

 

(B) Push 

Mounting

bracket

DIN rail

(A) Pull down

Locked 

 

Fig. 1   

Fig. 2 

 

 

End Plate mounting 

Hold tight both ends of the modules jointed together with the end 

plates and then fix the end plates with screws. Even if only one 
V-TIO-E/F module is used, also hold tight both ends of the 

module with the end plates. 

 

End Plate

V-TIO-E/F module 

End Plate

Joint connector cover 

*

 

 

For the conservation of the contact of connector, install a joint 
connector cover in module of both ends.

 

 

 

Removing procedures 

Pull down a mounting bracket with a blade screwdriver (A). Lift 
the module from bottom, and take it off (B). 

 

(A) Pull down 

(B) Lift and take off 

 

 

 

 

 
To prevent electric shock or instrument failure, 
always turn off the power before mounting or 
removing the instrument. 

!

 

WARNING 

Summary of Contents for V-TIO-E

Page 1: ...osed instrumentation panel All high voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions desc...

Page 2: ...groups and then installed Usable modules Temperature control TIO module Basic type V TIO A C Temperature control TIO module Extension type V TIO B D Up to 30 modules Event input output connector optio...

Page 3: ...JPt100 P17 0 to 400 C PC5 32 to 752 F P23 0 to 600 C PC4 32 to 1112 F P16 0 0 to 400 0 C PC7 32 0 to 752 0 F P28 200 0 to 400 0 C PC6 328 0 to 752 0 F Voltage current input Code Type Code Type Voltage...

Page 4: ...e See P 5 Set the unit address for PLC communication PLC communication setting switch left side See P 5 Set the communication speed data bit configuration and protocol for PLC communication Set the sa...

Page 5: ...imal Factory set value 0 9 8 7 C B A 6 543 2 1 0 F E D Address setting switch 2 for unit address PLC communication Up to four V TIO E F modules can be connected to a PLC communication port Therefore t...

Page 6: ...ps ON ON 38400 bps Factory set value 9600 bps 3 4 5 Data bit configuration OFF OFF OFF Data 7 bit without parity Stop 1 bit OFF OFF ON Data 7 bit Even parity Stop 1 bit OFF ON OFF Don t set this one O...

Page 7: ...y reach of the operator It shall be marked as the disconnecting device for the equipment 5 2 Dimensions Unit mm 110 6 8 40 5 125 78 5 The above figure shows when provided with the event input output c...

Page 8: ...se induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could aff...

Page 9: ...e modular connector should be used for the connection to the V TIO E F module Recommended manufacturer and model Hirose Electric TM4P 66P Event input output connector 1 6 Event input output connector...

Page 10: ...low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Option Event input Number of inputs 1 point Input type Dry contact...

Reviews: