IMS01P04-E4
5
4.1 Address Setting
Set an address. For this setting, use a small blade screwdriver.
To avoid problems or malfunction, do not duplicate
an address on the same communication line.
Module address setting
When using two or more modules, set the desired address to
each module.
(Common to PLC communication and host communication)
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
High-order digit setting
(set value
×
10)
Setting range: 0 to 30
(Factory set value: 0)
Low-order digit setting
(set value
×
1)
Address setting switch 1 (for module address)
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVENT4
5
4
3
2
1
0
9 8 7
6
5
5
4
3
2
1
0
9 8 7
6
5
Module address setting differs depending on operation mode
selection address settings.
Free setting (factory set value)
Free settings can be made in the range of 0 to 30.
Continuous setting
Set the V-TIO-E/F module address to 0 and also set other
module addresses to consecutive numbers starting from 1.
When in the free setting, regardless of the number of
modules connected when the power is turned on, much
time is required until module recognition operation
comes to an end compared to the continuous setting as
this operation is performed to addresses from 0 to 30.
For operation mode selection address settings, see the
Module Type Controller SRV PLC/Host
Communication Instruction Manual (IMS01P05-E )
.
Unit address setting
When two or more V-TIO-E/F modules are multi-drop connected,
set an address to each V-TIO-E/F module. This becomes the
unit address of the SRV unit.
(Common to PLC communication/host communication)
Left side
Setting range:
0 to 15 [0 to F: hexadecimal]
(Factory set value: 0)
9
8
7
C
B
A
6 5 4 3
2
1
0
F
E
D
Address setting switch 2
(for unit address)
PLC communication
Up to four V-TIO-E/F modules can be connected to a PLC
communication port. Therefore the unit address uses the four
V-TIO-E/F modules as a group. For V-TIO-E/F modules which
are multi-drop connected to the same PLC communication port,
use successive numbers assigned to any one of four groups
shown in the following table as their addresses.
Group
Address setting
switch 2
Group
Address setting
switch 2
Group 1
0
Group 3
8
1
9
2
A
3
B
Group 2
4
Group 4
C
5
D
6
E
7
F
Always set the unit address of each group including
0, 4, 8 or C. 0, 4, 8 or C becomes the master for
communication transfer.
Host communication
Differently from PLC communication, there are no group
restrictions. Free settings can be made in the range of 0 to F.
For Modbus, the value obtained by adding “1” to the
set address corresponds to the address used for the
actual program.
4.2 Protocol Selections and
Communication Speed Setting
PLC
communication setting switc
h
Set the communication speed, data bit configuration, and
protocol for PLC communication and host communication 2.
In addition, select the communication port of modular connector.
Left side
PLC communication
setting switch
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
ON
OFF
1
2
Data bit configuration
OFF OFF
Data 8-bit, without parity, Stop 1-bit
ON
OFF
Data 7-bit
*
, Odd parity, Stop 1-bit
OFF
ON
Data 7-bit
*
, Even parity, Stop 1-bit
ON
ON
Data 7-bit
*
, Even parity, Stop 2-bit
*
To be changed to data 8-bit only when “Host communication 2
(Modbus)” is selected.
Factory set value: Data 8-bit, without parity, Stop 1-bit
3 4
Communication
speed
OFF OFF
9600 bps
ON
OFF
19200 bps
OFF
ON
38400 bps
ON
ON
Don’t set this one
Factory set value: 9600 bps
Continued on the next page.