3.4
Operating conditions
The CMC III PU may only be operated under the following operating conditions:
4
Assembly
4.1
Assembly instructions
The assembly of the CMC III PU is made as shown in fig. 2.
Mount the CMC III PU so that the front with the transmitter and receiver is pointing to the moni-
tored door.
Stick the enclosed reflecting foil on the door and the side wall exactly opposite of the integrated
infrared access sensor.
5
Installation and operation
5.1
Operating and display elements
The operating and display elements are shown in fig. 3.
Key for fig. 3
1
"C" key to acknowledge messages
2
Hidden reset key
3
Multi-LED for the status display
4
SD card slot (not for the "Compact" variant)
5
Integrated infrared access sensor
6
Mini USB connection for configuring
7
Digital inputs (two), per 24 V
, 10 mA
8
USB master connection (not for the "Compact" variant)
9
Connection of an external temperature sensor
Temperature operational range
+0°C…+45°C
Humidity operational range
5%…95% relative humidity, non-condensing
Protection category
IP 30 according to IEC 60 529
Note:
We recommend that the network settings are changed before the device is installed
(see section 6).
Note:
To permit the exact temperature measurement with the internal temperature sensor,
an adequate air circulation in the enclosure or server enclosure must be provided,
and the CMC PU III located so that it is adequately supplied with air, and the vent slots
not covered.
If this cannot be implemented, the external temperature sensor from the scope of sup-
ply must be used instead of the internal temperature sensor.
Note:
The separation between the infrared access sensor in the CMC III PU and the reflect-
ing foil must not exceed 15 cm. If necessary, correct the CMC III PU installation loca-
tion appropriately.