NOTICE
Faulty release due to removal of the blocking!
Premature removal of the blocking can result in a faulty release and thereby cause
property damage.
● Do not stop blocking the system until there are no red LEDs lit up and there is
no fire alarm shown in the display.
5.2.5.2
Manual call point
L
CAUTION
Danger of injury from faulty release!
Checking the manual call point when the system is not blocked can result in a faulty
release. A faulty release may cause injuries and significant property damage.
● Block the system prior to checking the manual call point. To this end, switch the
blocking switch on the back of the system to the
Ⅱ
"Agent disconnect
[blocked]" position.
Ⅰ
Agent connect [not blocked]
Ⅱ
Agent disconnect [blocked]
Connect the manual call point as per
Chapter 5.3.5 „Manual call point”
to connection "manual call
Reset the failure message that comes up when connecting with the upper
[Reset]
button.
After the manual call point is released, the lower red LED blinks and
„Manual
release”
and
„Fire”
are shown in the display.
Reset the manual call point and activate the system again with the upper
[Reset]
button.
Fig. 23: Blocking switch
Fig. 24: Connection manual call point