background image

G.   SYSTEM EVACUATION (SPLIT SYSTEM ONLY) 

1.

 

With refrigerant piping completed and leak tested, equipment is ready to evacuate.  Do not use compressor to evacuate system.  A 
quality  vacuum pump capable of 350 micron  vacuum  is necessary  for adequate and dependable system  vacuum.  Moisture in a 
refrigeration system can cause corrosion, expansion valve freeze-up and oil sludge. 

2.

 

attach  vacuum  pump  to  both  high  and  low  side  of  system  through  compressor  service  valves  and  evacuate  to  350  microns  (all 
service valves, hand valves, and solenoids must be open during evacuation).  It is suggested that vacuum pump be run for a period 
of time after vacuum has been reached. 

3.

 

Service should be provided by a qualified EPA refrigeration technician only. 

 

H.   START-UP 

1.

 

This will involve checking and adjusting of all safety and operation controls (pressure and temperature controls have been set at 
the  factory;  however, it is still desirable to confirm  that settings are correct and controls function properly).   Do not attempt to 
disengaged  or  bypass  safety  controls  without  some  means  of  stopping  compressor  in  event  of  extreme  high  or  low  pressure 
conditions that could damage the equipment.  If controls fail to function at set point, determine cause and correct.  Jumping any 
safety control other than for testing purposes is dangerous to personnel and equipment, and nullifies equipment warranty. 

2.

 

The  bottom  opening  is  the  pump  outlet  to  your  process.    The  bottom  opening  is  the  pump  outlet  to  your  process.    The  middle 
opening is the return inlet water coming back to the reservoir tank.  Fit a union and a tee in the return line.  Bring the make-up 
water line to the tee.  This is used to fill the chiller and system. 

3.

 

With the chiller switch OFF, turn on the MAINPOWER to the chiller.  Even though the chiller switch is off, the main power will 
activate  the  compressor  crankcase  heater  to  warm  up  the  oil  and  burn  off  any  Freon  that  has  migrated  into  the  crankcase  (this 
feature is standard in ALL compressors with the exception of scrolls).  Allow the compressor(s) to warm overnight, or at least six 
hours.  This is a one time procedure for start-up.  However, if the main power is off for over 24 hours, (four hours if outside in 
cold weather), then the warm-up procedure should be repeated. 

4.

 

To fill chiller, open the city water and fill at a SLOW RATE.  When water comes out of the ½” top vent opening it means the 
reservoir  tank  is  full.    SHUT  WATER  OFF.    Open  all  valves  to  process  and  start  chiller  for  about  15  seconds  to  fill  lines  and 
equipment.  STOP CHILLER.  Open city water again at a SLOW RATE till water again comes out of the vent pipe.  SHUT THE 
WATER OFF.  The system is full and ready for use. 

 

I.   SHUT DOWN 

1.

 

Equipment  which  will  not  be  required  to  operate  for  a  period  of  time  should  be  secured  by  storing  refrigerant  charge  in  the 
receiver or condenser.  On units with coolers or water cooled condensers, special precautions must be taken to completely drain 
the vessels to prevent freezing if ambient should be below 32*F. 

2.

 

Inspect system for possible worn or faulty components and repair if required. 

 

J.    SYSTEM RESTART AFTER SHUT DOWN 

1.

 

Thorough leak test should be performed. 

2.

 

Coil(s) should be checked for dirt accumulation or obstruction and cleaning if necessary. 

3.

 

Refill water system and purge all air from system. 

4.

 

Energize crankcase heaters and allow a minimum of 12 hours operation before compressor restart. 

5.

 

Install gauges, start system and check for correct refrigerant charge, and proper system operation and balance. 

 

K.   MAINTENANCE 

1.

 

The system should be checked periodically.  Use only the services of an EPA qualified refrigeration technician for inspection and 
maintenance checks or service operations. 

2.

 

Water Treatment (Chillers and Water Cooled Condensing Units) – The water should be tested by a local testing agency and their 
recommendations adhered to. 

3.

 

Air  Cooled  Condenser  –  The  inlet  side  of  the  condenser  coil  must  be  kept  clean  through  a  regular  prevention  maintenance 
program. ] 

4.

 

Periodically checks all electrical connections for possible loose or corroded terminals.  Repair as necessary. 

 
 
 
 
 
 
 
 

Summary of Contents for R422D

Page 1: ...rite temp INSTALLATION MAINTENANCE GUIDE WATER CHILLERS...

Page 2: ...ping guide Engineering Guide 1 for air conditioning systems 3 Water piping Chillers should be designed and installed to meet application requirements Provisions Ethylene or Propylene Glycol must be ma...

Page 3: ...this feature is standard in ALL compressors with the exception of scrolls Allow the compressor s to warm overnight or at least six hours This is a one time procedure for start up However if the main...

Page 4: ...000 1 4 1 4 1 4 1 4 3 000 3 8 3 8 3 8 3 8 4 500 1 4 1 4 3 8 3 8 4 500 3 8 3 8 1 2 1 2 6 500 1 4 1 4 3 8 3 8 6 500 3 8 1 2 1 2 1 2 8 500 1 4 3 8 3 8 3 8 8 500 3 8 1 2 1 2 5 8 12 000 3 8 3 8 3 8 1 2 12...

Page 5: ...ater pipe DO NOT plumb w ith smaller size pipe than noted on this print The bypass line is necessary if units to be cooled have self acting shut off valves Water must circulate through chiller at all...

Page 6: ...circuit or burnout i Loose wiring i Check all wire junctions Tighten all terminal screws Compressor noisy or vibrating a Flooding of refrigerant into crankcase a Check setting of expansion valve b Im...

Page 7: ...refrigerant a Check or leaks Repair and add charge b Evaporator dirty b Clean chemically c Clogged liquid line filter drier c Replace cartridge s d Clogged suction line or compressor suction gas strai...

Page 8: ...ty switch defective d Replace e Worn oil pump e Replace f Oil pump reversing gear stuck in wrong position f Reverse direction of compressor rotation g Worn bearings g Replace compressor h Low oil leve...

Page 9: ...ot start until fault is corrected f High ambient temperature around the overload relay f Provide ventilation to reduce heat g Failure of second starter to pull in on part winding start system g Repair...

Page 10: ...original Purchaser User that products manufactured by Rite Temp shall be free from defects in material and workmanship under normal use and service for a period of twelve months from date of shipment...

Page 11: ...DO NOT USE AUTOMOTIVE OR RV ANTI FREEZE RITE TEMP RECOMMENDS USING EITHER ETHYLENE GLYCOL OR PROPYLENE GLYCOL...

Page 12: ...rite temp Water Chillers Distributed By RITE TEMP MANUFACTURING INC PO BOX 1275 1704 S 1ST STREET ROGERS AR 72757 800 462 3120 PH 479 986 0727 FAX www ritetemp com...

Reviews: