background image

TROUBLESHOOTING 

 

Compressor will not run.

 

a) Main switch open. 
Circuit breakers open

 

a) Close switch

 

b) Fuse blown

 

b) Check electrical circuits and motor winding for shorts or grounds. Investigate   
for possible overloading. Replace fuse or reset breakers after fault is corrected.

 

c) Thermal overloads 
tripped or fuses blown

 

c) Overloads are auto. Reset. Check unit closely when unit comes back on line.

 

d) Defective contactor or 
coil

 

d) Repair or replace

 

e) System shut down by 
safety devices

 

e) Determine type and cause of shut-down and correct it before resetting safety 
switch.

 

f) No cooling required

 

f) None. Wait until unit calls for cooling.

 

g) Liquid line solenoid 
will not open

 

g) Repair or replace coil

 

h) Motor electrical trouble

 

h) Check motor for opens, short circuit, or burnout

 

i) Loose wiring

 

i) Check all wire junctions. Tighten all terminal screws.

 

  

 

Compressor noisy or vibrating.

 

a) Flooding of refrigerant into crankcase

 

a) Check setting of expansion valve

 

b) Improper piping support on discharge coil or liquid 
line*

 

b) Relocate, add, or remove hangers

 

c) Worn compressor

 

c) Replace

 

  

 

High Discharge Pressure

 

a) Condenser water insufficient or temperature too 
high

 

a) Readjust water regulating valve. Investigate ways 
to increase water supply

 

b) Fouled condenser tubes (water cooled 
condenser). Clogged spray nozzles (evaporative 
condenser). Dirty tube and fin surface (air cooled 
condenser)

 

b) Clean

 

c) Non-condensable in system

 

c) Purge the non-condensables

 

d) System overcharged with refrigerant*

 

d) Remove excess

 

e) Discharge shut off valve partially dosed

 

e) Open valve

 

f) Condenser undersized*

 

f) Check condenser rating tables against the 
operation

 

g) High ambient conditions*

 

g) Check condenser rating tables against the 
operation

 

  

Summary of Contents for R422D

Page 1: ...rite temp INSTALLATION MAINTENANCE GUIDE WATER CHILLERS...

Page 2: ...ping guide Engineering Guide 1 for air conditioning systems 3 Water piping Chillers should be designed and installed to meet application requirements Provisions Ethylene or Propylene Glycol must be ma...

Page 3: ...this feature is standard in ALL compressors with the exception of scrolls Allow the compressor s to warm overnight or at least six hours This is a one time procedure for start up However if the main...

Page 4: ...000 1 4 1 4 1 4 1 4 3 000 3 8 3 8 3 8 3 8 4 500 1 4 1 4 3 8 3 8 4 500 3 8 3 8 1 2 1 2 6 500 1 4 1 4 3 8 3 8 6 500 3 8 1 2 1 2 1 2 8 500 1 4 3 8 3 8 3 8 8 500 3 8 1 2 1 2 5 8 12 000 3 8 3 8 3 8 1 2 12...

Page 5: ...ater pipe DO NOT plumb w ith smaller size pipe than noted on this print The bypass line is necessary if units to be cooled have self acting shut off valves Water must circulate through chiller at all...

Page 6: ...circuit or burnout i Loose wiring i Check all wire junctions Tighten all terminal screws Compressor noisy or vibrating a Flooding of refrigerant into crankcase a Check setting of expansion valve b Im...

Page 7: ...refrigerant a Check or leaks Repair and add charge b Evaporator dirty b Clean chemically c Clogged liquid line filter drier c Replace cartridge s d Clogged suction line or compressor suction gas strai...

Page 8: ...ty switch defective d Replace e Worn oil pump e Replace f Oil pump reversing gear stuck in wrong position f Reverse direction of compressor rotation g Worn bearings g Replace compressor h Low oil leve...

Page 9: ...ot start until fault is corrected f High ambient temperature around the overload relay f Provide ventilation to reduce heat g Failure of second starter to pull in on part winding start system g Repair...

Page 10: ...original Purchaser User that products manufactured by Rite Temp shall be free from defects in material and workmanship under normal use and service for a period of twelve months from date of shipment...

Page 11: ...DO NOT USE AUTOMOTIVE OR RV ANTI FREEZE RITE TEMP RECOMMENDS USING EITHER ETHYLENE GLYCOL OR PROPYLENE GLYCOL...

Page 12: ...rite temp Water Chillers Distributed By RITE TEMP MANUFACTURING INC PO BOX 1275 1704 S 1ST STREET ROGERS AR 72757 800 462 3120 PH 479 986 0727 FAX www ritetemp com...

Reviews: