background image

IMPORTANT – READ BEFORE INSTALLING 

 
 

INSTALLATION INSTRUCTIONS 

 
A.   RECEIVING AND INSPECTION 

1.

 

Immediately upon receiving shipment, equipment should be inspected for evidence of any damage received in transit.  If shipping      
damage has occurred, a claim should be made with the transportation company, and the local Rite-Temp representative should be 
advised of nature of damage. 

2.

 

Equipment should be inspected for compliance with original order acknowledgement (equipment model numbers, voltages, etc.). 

 

B.   RIGGING 

1.

 

Equipment should be lifted in a near level condition to prevent undue stress on structural members. 

 

C.   MOUNTING 

1.  Equipment should be mounted on a smooth, hard, level surface. 
2.

 

Mounting surface should be rigid, and provisions should be made to prevent noise transmission (structural) to surrounding areas. 

3.

 

Air  cooled  equipment  should  not  be  installed  under  low  structural  overhangs  which  can  cause  condenser  air  recirculation  or 
restriction. 

4.

 

Adequate Area (approx. 1 unit width) must be provided around equipment for unrestricted air flow and service.  Two units side by 
side should have a minimum of 1 ½ unit width between them. 

5.

 

Care should be taken to prevent air from other sources from entering condenser if this air is at an elevated temperature. 

6.

 

Indoor design equipment must be installed in a protected enclosure. 

 

D.   PIPING 

1.

 

All piping must be in accordance with applicable local and state codes. 

2.

 

Refrigerant piping (split systems) should be designed and installed in accordance with recommended practices as outlined in ARI 
or ASHRE piping guide.   

(Engineering Guide #1 for air conditioning systems.) 

3.

 

Water  piping  (Chillers)  should  be  designed  and  installed  to  meet  application  requirements.  Provisions  (Ethylene  or  Propylene 
Glycol) must be made to prevent freezing if design ambient temperatures dictate. 

4.

 

When  piping  is  completed,  a  thorough  leak  test  should  be  performed  before  evacuation  start-up.    Do  not  exceed  150  psig  test 
pressure on low side of system. 

 

E.   WIRING 

1.

 

All  local  and  state  codes  must  be  strictly  adhered  to  and  good  electrical  practices  should  be  followed  to  achieve  the  best 
installation possible. 

2.

 

Power wiring to equipment must be adequately sized for minimum ampacity as shown on unit nameplate.  A disconnect should be 
located adjacent to unit for both safety and servicing purposes. 

3.

 

Equipment wiring diagram should be examined and thoroughly understood before field wiring connections are made. 

4.

 

Power  supply  should  be  checked  to  be  certain  that  supply  voltage  agrees  with  equipment  nameplate.    Serious  damage  to 
compressors and motors can occur if improper voltage is applied. 

5.

 

Use copper conductors ONLY. 
 

F.   ROTATION DIRECTION OF THREE PHASE SCROLL COMPRESSORS 

1.

 

Scroll  compressors  will  only  compress  in  one  rotational  direction.    Direction  of  rotation  is  not  an  issue  with  single  phase 
compressors  since  they  will  always  start  and  run  in  the  proper  direction.    Three  phase  compressors  will  run  in  either  direction 
depending  upon  the  phasing  of  the  power.   

Verification  of  proper  rotational  direction  must  be  made

  by  observing  that  the 

suction  pressure  drops  and  the  discharge  pressure  rises  when  the  compressor  is  energized.    Reverse  rotation  also  results  in  an 
elevated sound level as well as substantially reduced current draw compared to forward rotation. 

 
 
 
 
 
 
 

Summary of Contents for R422D

Page 1: ...rite temp INSTALLATION MAINTENANCE GUIDE WATER CHILLERS...

Page 2: ...ping guide Engineering Guide 1 for air conditioning systems 3 Water piping Chillers should be designed and installed to meet application requirements Provisions Ethylene or Propylene Glycol must be ma...

Page 3: ...this feature is standard in ALL compressors with the exception of scrolls Allow the compressor s to warm overnight or at least six hours This is a one time procedure for start up However if the main...

Page 4: ...000 1 4 1 4 1 4 1 4 3 000 3 8 3 8 3 8 3 8 4 500 1 4 1 4 3 8 3 8 4 500 3 8 3 8 1 2 1 2 6 500 1 4 1 4 3 8 3 8 6 500 3 8 1 2 1 2 1 2 8 500 1 4 3 8 3 8 3 8 8 500 3 8 1 2 1 2 5 8 12 000 3 8 3 8 3 8 1 2 12...

Page 5: ...ater pipe DO NOT plumb w ith smaller size pipe than noted on this print The bypass line is necessary if units to be cooled have self acting shut off valves Water must circulate through chiller at all...

Page 6: ...circuit or burnout i Loose wiring i Check all wire junctions Tighten all terminal screws Compressor noisy or vibrating a Flooding of refrigerant into crankcase a Check setting of expansion valve b Im...

Page 7: ...refrigerant a Check or leaks Repair and add charge b Evaporator dirty b Clean chemically c Clogged liquid line filter drier c Replace cartridge s d Clogged suction line or compressor suction gas strai...

Page 8: ...ty switch defective d Replace e Worn oil pump e Replace f Oil pump reversing gear stuck in wrong position f Reverse direction of compressor rotation g Worn bearings g Replace compressor h Low oil leve...

Page 9: ...ot start until fault is corrected f High ambient temperature around the overload relay f Provide ventilation to reduce heat g Failure of second starter to pull in on part winding start system g Repair...

Page 10: ...original Purchaser User that products manufactured by Rite Temp shall be free from defects in material and workmanship under normal use and service for a period of twelve months from date of shipment...

Page 11: ...DO NOT USE AUTOMOTIVE OR RV ANTI FREEZE RITE TEMP RECOMMENDS USING EITHER ETHYLENE GLYCOL OR PROPYLENE GLYCOL...

Page 12: ...rite temp Water Chillers Distributed By RITE TEMP MANUFACTURING INC PO BOX 1275 1704 S 1ST STREET ROGERS AR 72757 800 462 3120 PH 479 986 0727 FAX www ritetemp com...

Reviews: