22
Pub. No. 1120-R5 — June 2000
1L2 (Black)
G (Green)
Motor
Thermal
Overload
Motor – 3/4 HP
@2850/3450 R.P.M.
240V 1 PH 50/60 Hz
Intermittent Duty
(Thermally Protected
With Automatic Reset)
Use Minimum #14 Gage, 60
°
/ 75
°
C Copper
Wire/100 Ft. Of Run – 15 Amp Circuit 240V.
Consult Local Code.
– Wire Termination
Wire Nut Or Equal Device
MOTOR LEAD CONNECTIONS
L1 L2 G
1L1 1L2 G
NOTES:
1. PB1 “RAISE” Switch Is 1 HP Rated.
2. Optional Recycle Limit Switch LS1 Is Automatically Operated By
The Location Of The Hydraulic Cylinder. This In Turn Controls
Flow To LS2 Which Is Operated By The Lip Assist Push Rod
Assy. Both Switches Are 1 HP Rated (APB-1000 Only).
3. For Field Wiring See Dwg. #AI-1839.
LS1 (N.O.H.C.)
Restrictor Switch
(Held Closed)
LS2 (N.O.)
ARTD Limit Switch
(Automatic Return To Dock)
Optional (APB-1000 Only)
2L1
(White
w/Red
Marker)
T1/P1
(White
w/Red
Marker)
1L1
(Black)
2L1
(Black)
4425
1L1 (Red)
T1 (Black)
One Leveler Per Overload Protection Device.
(Ref. N.E.C. 1996 Para. 430-110 (C)) Consult Local Code.
A Branch Circuit Disconnect Shall Be Located No More
Than 50' From The Control Box And Must Be Visible.
(Ref. N.E.C. 1996 Para. 430-102 (A) And Article 100).
BRANCH
CIRCUIT
DISCONNECT
From Customer Main Power & Safety
Protection Device 240V 1 PH 50/60 Hz.
(Fused Disconnect Supplied By Others)
(Must Use Either 10 Amp Dual Element
Fuse Or 15 Amp Inverse Time Circuit
Breaker).
PUSHBUTTON
CONTROL BOX
G (Green)
G (Green)
1L2 (Black)
T5
T4
T2
T8
T3
P2
P1
T1/ P1 (White / Red)
2L1
(White / Red)
2L1 (Black)
1L1 (Red)
1L1 (Black)
Motor
MOTOR JUNCTION BOX
ELECTRICAL SCHEMATIC 240V WITH AUTOMATIC RETURN TO DOCK (ARTD) OPTION
4425 Rev C
FIGURE 24 — ELECTRICAL SCHEMATIC, 240V WITH ARTD
APB-1000/Rev5 6/1/00 7:48 AM Page 22