![Rishabh RISH CON - I Operating Manual Download Page 54](http://html1.mh-extra.com/html/rishabh/rish-con-i/rish-con-i_operating-manual_1464362054.webp)
Auxiliary
AC/DC Auxiliary Supply
60V….300 VAC-DC ±5%
24V….60 VAC-DC ±10%
Auxiliary Supply
40......65 Hz
frequency range
Auxiliary Supply consumption
Measuring Output Y (
Single or Optional Dual
)
Output type
Load independent DC Voltage or
DC Current (Onsite selectable
through DIP switches &
Programming.)
Load independent DC -
0…20mA / 4…20mA OR
output
0…10V.
Output burden with DC
0 < R < 15V/Y2
current output Signal
Output burden with DC
Y2/(2 mA)< R <
∞
voltage output Signal
Current limit under
< 1.25 * Y2 with current output
overload R=0
< 100 mA with Voltage output
Voltage limit under R=
∞
< 1.25 * Y2 with voltage output
< 30 V with current output
Residual Ripple in
<1% pk-pk
Output signal
Response Time
< 400 ms.
52
VA for one output
£
8
£
10VA for two outputs
60V…….300 VAC-DC
24V…….60 VAC-DC
VA for one output
£
5
£
6VA for two outputs
Summary of Contents for RISH CON - I
Page 1: ...IC 15001063 REV C 17 12 13 Operating Manual I Programmable Current Transducer RISH CON I...
Page 2: ......
Page 59: ...5 6 7 8 1 2 3 4 Input I Aux Output 1 Output 2 Optional 57...
Page 61: ...Notes 59...
Page 62: ...Notes 60...
Page 64: ...Notes 62...