When PAN08 detect a overload power, it will report alarm to Group1
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08, Alarm Level = 0xFF
(Overload)]
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x08, Alarm Level = 0x00
(Normal)]
When in Two Push Button switch type, S1 or S2 are closed and not released to open,
and PAN08 receive any control moving command from Z-Wave RF, it will report
alarm to Group1.
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x01, Alarm Level = 0xFF
(S1 or S2 close to L)]
[Command_Class_Alarm, Alarm_Report, Alarm Type = 0x01, Alarm Level = 0x00
(S1 and S2 released from L)]
7
Z-Wave’s Configuration
Configuration
Parameter
Function
Size
(Byte)
Value
Unit
Default Description
1
Watt
Meter
Report
Period
2
0x01-
0x7FFF
5s
720
5*720s=3600s=1
hour
2
KWH
Meter
Report
Period
2
0x01-
0x7FFF
10
min
6
6*10min= 1 hour
3
Threshold
of current
for Load
Caution
2
10-500
0.01
A
500
500*0.01A=5A
4
Threshold
of KWH
for Load
Caution
2
1-1000
0
1
KWh
10000
5
External
switch
type
1
1-2
2
1:
One Push button
2:
Two Push button
6
Level
report
mode
1
1-2
2
1:
Report destination
level in 5s
2:
Report 10 percent
level while
running
7-1 Watt Meter Report Period:
If the setting is configured for 1hour (set value =720), the PAN08 will report its instant
power consumption every 1 hour to the node of Group 1. The maximum interval to
report its instant power consumption is 45 hours (5s*32767/3600=45hr). Default
value is 1 hour.
7-2 KWH Meter Report Period:
If the setting is configured for 1hour (set value =6), the PAN08 will report its
Accumulated Power Consumption (KW/h) every 1 hour to the node of correspond
Group. The maximum interval to report its Accumulated Power Consumption (KW/h)
is 227.55 days (10min*32767/1440=227.55 days). Default value=1 hour.
7-3 Threshold of current for Load Caution
This is a warning when the current of load over the preset threshold value, if the
setting value is 500, when the load current of Relay1 over this value, PAN08
will send current meter report to warn the Group1 node, the Range of the setting
value is from 10 to 500, and the default value is 500.
7-4 Threshold of KWh for Load Caution
This is a warning when the KWh of load over the preset threshold value, If the setting
value is 10000, when the Accumulated Power Consumption of Relay1 or Relay2 over
this value, PAN08 will send KWh Meter Report command to the node of correspond
Group, minimum value is 1KWh and default value is 10000 kWh
7-5 External switch type
7-5-1 One Push Button
: