Value Series Manual 

Installation of Plumbing 

A manual water control valve must be placed in the 
water inlet connection to the water heater before it is 
connected to the water line.  Unions may be used on 
both the hot and cold water lines for future servicing 
and disconnection of the unit. 

DO NOT 

 

Do not introduce toxic chemicals such as those 
used for boiler water treatment to the potable 
water used for space heating. 

MUST DO 

 

The piping (including soldering materials) and 
components connected to this appliance must be 
approved for use in potable water systems. 

 

Purge the water line to remove all debris and air.  
Debris will damage the water heater. 

 

If the appliance will be used as a potable water 
source, it must not be connected to a system that 
was previously used with a nonpotable water 
heating appliance. 

 

Ensure that the water filter on the water heater is 
clean and installed. 

Piping Requirements 

Pressure Relief Valve Requirements 

Install the pressure relief valve according to local 
plumbing codes and these instructions.   

An approved pressure relief valve is required by the 

American National Standard (ANSI Z21.10.3) 

for all 

water heating systems, and shall be accessible for 
servicing. 

DO NOT 

 

Do not plug the relief valve and do not install any 
reducing fittings or other restrictions in the relief 
line.  The relief line should allow for complete 
drainage of the valve and the line.

 

 

Do not place any other type valve or shut off 
device between the relief valve and the water 
heater.

 

MUST DO 

 

The relief valve must comply with the standard for 

Relief Valves and Automatic Gas Shutoff Devices for 
Hot Water Supply Systems ANSI Z21.22

 and /or the 

standard 

Temperature, Pressure, Temperature and 

Pressure Relief Valves and Vacuum Relief Valves, 
CAN1-4.4

.   

 

The relief valve must be rated up to 150 psi and to 
at least the maximum BTU/hr of the appliance. 

 

The discharge from the pressure relief valve should 
be piped to the ground or into a drain system to 
prevent exposure or possible burn hazards to 
humans or other plant or animal life.  Follow local 
codes.  Water discharged from the relief valve 
could cause severe burns instantly, scalds, or 
death. 

 

The pressure relief valve must be manually 
operated once a year to check for correct 
operation. 

 

The relief valve should be added to the hot water 
outlet line and near the hot water outlet according 
to the manufacturer’s instructions.   DO NOT place 
any other type valve or shut off device between 
the relief valve and the water heater. 

INFORMATION 

 

If a relief valve discharges periodically, this may be 
due to thermal expansion in a closed water supply 
system.  Contact the water supplier or local 
plumbing inspector on how to correct this 
situation.  Do not plug the relief valve. 

 

The 

American National Standard (ANSI Z21.10.3) 

does not require a combination temperature and 
pressure relief valve for this appliance.  However, 
local codes may require a combination 
temperature and pressure relief valve. 

Isolation Valves 

Rinnai strongly recommends the installation of 
isolation valves on the cold and hot water lines 
because they provide the ability to isolate the water 
heater from the structure’s plumbing and allow quick 
access to flush the heat exchanger.  Flushing the heat 
exchanger regularly is required as part of the proper 
maintenance for this water heater. 

Summary of Contents for V65e

Page 1: ...to maintain the water heater If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death WARNING READ ALL OF THE IN...

Page 2: ...h Altitude 20 Adjust for Vent Length indoor models only 20 Checklist for Gas and Electricity 20 Installation of Temperature Controller 21 Final Checklist 23 Technical Data 24 Specifications 24 Dimensi...

Page 3: ...s appliance Always check the water temperature before entering a shower or bath To protect yourself from harm before performing maintenance Turn off the electrical power supply by unplugging the power...

Page 4: ...or to lower floors of the structure When such locations cannot be avoided it is recommended that a suitable drain pan adequately drained be installed under the appliance The pan must not restrict comb...

Page 5: ...turn off the manual gas control valve to the appliance Keep the air intake location free of chemicals such as chlorine or bleach that produce fumes These fumes can damage components and reduce the li...

Page 6: ...rmination Damage and repair due to corrosive compounds in the air is not covered by warranty Consideration of care for your water heater should include evaluation of water quality Water that contains...

Page 7: ...Installations A Clearance above grade veranda porch deck or balcony 12 inches 30 cm 12 inches 30 cm B Clearance to window or door that may be opened 36 inches 91 cm 12 inches 30 cm C Clearance to per...

Page 8: ...36 INSIDE CORNER V V 0 30 m to an inside corner 0 30 m between terminals at same level Important considerations for locating vent termination under a soffit ventilated or unventilated or eave vent or...

Page 9: ...tions near a dryer vent Avoid termination locations near commercial cooking exhaust Additional clearances V75e V65e 0 30 m to an inside corner 50 mm between terminals at same level 1 52 m vertically b...

Page 10: ...ce for servicing is 24 inches in front of the water heater to Combustibles inches mm to Non Combustibles inches mm Top of Heater 12 305 2 51 Back of Heater 0 zero 0 zero Front Panel 24 610 0 zero Fron...

Page 11: ...a diagnostic code The freeze protection features will not prevent the external piping from freezing It is recommended that hot and cold water pipes are insulated Pipe cover enclosures may be packed w...

Page 12: ...n must conform with the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 and or CAN SCA Z240 MH Series Mobile Homes Leave the entire manual taped to the water heater indoor mo...

Page 13: ...must use vent components that are certified and listed with the water heater model The vent system must vent directly to the outside of the building and use outside air for combustion Avoid dips or sa...

Page 14: ...t the bracket Secure the first vent component to the water heater with one self tapping screw at the hole located above the condensate collector Bracket Condensate Collector Securing Screw Horizontal...

Page 15: ...end should not be under water or other substances To minimize freezing of the condensate run the condensate drain line through an interior wall or between insulation and an interior wall The condensat...

Page 16: ...Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems ANSI Z21 22 and or the standard Temperature Pressure Temperature and Pressure Relief Valves and Vacuum Relief Valves CAN1 4...

Page 17: ...ng Pump Solenoid Valve Boiler Drain Valve KEY This is not an engineered drawing It is intended only as a guide and not as a replacement for professionally engineered project drawings This drawing is n...

Page 18: ...innai recommends 60 80 psi for maximum performance Installation of Gas Supply MUST DO A manual gas control valve must be placed in the gas supply line to the water heater A union can be used on the co...

Page 19: ...then the 3 4 inch pipe size is capable of supplying 273 FT3 HR of natural gas Gas Input of all gas products BTU HR Heating Value of Gas BTU FT 3 Cubic Feet per Hour CFH Any compound used on the thread...

Page 20: ...ee prong receptacle Do not cut or remove the grounding terminal from this plug Checklist for Gas and Electricity A manual gas control valve is placed in the gas line to the water heater Check the gas...

Page 21: ...2 164 ft 50 m 3 or 4 65 ft 20 m Turn the power off Do not attempt to connect the temperature controllers with the power on Although the controller is a low voltage device there is 120 volt potential n...

Page 22: ...ller to the wall using the holes drilled in step 1 6 Disconnect the power from the water heater 7 Remove the plastic cover from the PCB and electrical connections 8 Thread the cable through the access...

Page 23: ...inse the filter to remove any debris Install the filter and open the isolation valves Ensure that a pressure relief valve is installed with a rating that exceeds the BTU input of the water heater mode...

Page 24: ...ergy Factor 0 82 Noise level 49 dB excluding start up or shutdown Electrical Consumption Normal 76 W 76 W 57 W 57 W Standby 2 W Anti frost Protection 120 W 104 W Max Current Without recirculation pump...

Page 25: ...14 04 356 6 1 14 29 2 23 56 6 DIMENSION Inches mm DIMENSION Inches mm A GAS 1 31 33 2 D 4 33 110 A COLD 1 93 49 E 2 89 73 3 A HOT 1 35 34 4 F 1 85 47 B 4 21 106 9 G 3 44 87 3 C 1 17 29 8 Inches milli...

Page 26: ...30 00 35 00 40 00 45 00 50 00 55 00 60 00 0 1 2 3 4 5 6 7 8 Pressure Drop Curve Water Flow Curve V75i e Pressure Loss ft head Water Flow gpm Pressure Loss psi Water Flow gpm delta T Temperature Rise F...

Page 27: ...Value Series Manual 27 Ladder Diagram...

Page 28: ...and ask not to have your information shared We will however continue to contact you with information relevant to the product s you registered and or you account with us Do not store or use gasoline or...

Page 29: ...water TO TURN OFF GAS TO APPLIANCE 1 Turn off all electric power to the appliance using the ON OFF button 2 Set the thermostat to lowest setting 3 Locate the manual gas valve on the side of the heate...

Page 30: ...ine and other flammable vapors and liquids Always check the water temperature before entering a shower or bath Do not use this appliance if any part has been under water Immediately call a licensed pr...

Page 31: ...setting All hot water sources are able to provide water at this temperature setting until it is changed again at this or another temperature controller DANGER Hot water can be dangerous especially fo...

Page 32: ...ation a mixing valve must also be installed to limit the potable hot water temperature to a safe temperature Water temperatures over 125 F 52 C can cause severe burns or scalding Refer to the Danger A...

Page 33: ...he down button for 2 seconds and without releasing it press the ON OFF button To obtain the water flow rate press the up or down buttons until 01 displays The water flow rate will then appear For exam...

Page 34: ...regulator is sized properly Ensure gas type and pressure is correct Bleed all air from gas lines Ensure proper venting material was installed Ensure condensation collar was installed properly Ensure...

Page 35: ...ires Check all wiring to flame rod Remove flame rod and check for carbon build up clean with sand paper Check inside burner chamber for any foreign material blocking flame at flame rod Measure micro a...

Page 36: ...needs to be treated or conditioned When checking maintenance code history 00 is substituted for LC Snow Accumulation Keep the area around flue terminal free of snow and ice The appliance will not func...

Page 37: ...any issues resulting from the use of this information GAS Shut off the gas to the water heater It is generally preferable to shut off the gas service to the entire location if gas is not going to be u...

Page 38: ...iluted virgin food grade white vinegar into pail 6 Place the drain hose H3 and the hose H2 to the pump inlet into the cleaning solution 7 Open both service valves V1 and V2 on the hot water and cold w...

Page 39: ...g that the temperature controller is off turn on the gas supply 8 Turn on the temperature controller Running a low volume of water through the water heater to prevent freezing If the temperature excee...

Page 40: ...er to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a In the event that the side wall horizontally vented gas fueled equipment is...

Page 41: ...s Servo Assembly 403 Water Filter Assy 412 PC Board 700 Ignitor 706 Thermal Fuse Harness 725 Ignitor Thermal Fuse Harness Bypass Servo Assembly Water Filter Assy PC Board Water Flow Servo Sensor Fan A...

Page 42: ...in material or workmanship or damaged by improper installation or damaged during return shipping the warranty claim for product parts and labor may be denied How do I get service You must contact a s...

Page 43: ...ons This Limited Warranty does not apply to any product whose serial number or manufacture date has been defaced This Limited Warranty does not cover any product used in an application that uses chemi...

Page 44: ...pareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareil Ne touchez aucun interrupteur ne pas vous servir des t l phones se trouvant dans le b timent Appelez imm diatement v...

Page 45: ...u chauffe eau 74 Garantie du consommateur 75 Indication d une situation imminente dangereuse qui si elle n est pas vit e peut entra ner des blessures graves voire mortelles Indication d une situation...

Page 46: ...mais tre stock dans les environs de cela ou tout appareil de gaz Toujours v rifier la temp rature de l eau avant d entrer dans une salle de bains ou douche Pour vous prot ger contre les pr judices ava...

Page 47: ...xt rieur Le V75e et V65e n est pas pr vu pour une installation l int rieur N installez pas l appareil dans une r gion o les fuites d eau de l unit ou les connexions se traduira par dommages la zone ad...

Page 48: ...ez l arriv e de gaz au niveau de la vanne de contr le manuelle alimentant l appareil Gardez la zone d aspiration d air exempte de produits chimiques comme chlore ou agent de blanchiment qui produisent...

Page 49: ...de la cessation de chauffage ou de vent de l eau Dommages et r paration en raison de compos s corrosifs dans l air n est pas couvert par la garantie Examen de diligence pour votre chauffe eau devrait...

Page 50: ...timent ou entr e d air de combustion vers tout autre appareil 36 91 cm 12 30 cm K cartement par rapport entr e d alimentation d air m canique 6 1 83 m 3 91 cm au dessus si 10 3 m horizontalement L Esp...

Page 51: ...orche l int rieur coin V75i V65i 1 52 m verticalement entre les bornes 12 12 36 INSIDE CORNER V V 0 30 m l int rieur coin 0 30 m entre terminaux au m me niveau l int rieur coin Des consid rations impo...

Page 52: ...610 mm sur l avant du chauffe eau Pour installation en placard espacement de 6 pouces 152 mm l avant Mod les d int rieur V75i V65i Jusqu mati res combustibles pouces mm Jusqu mati res non combustible...

Page 53: ...tre emball s avec isolation pour la protection de l ajout de gel En cas de panne de courant des temp ratures de cong lation de l eau r chauffeur devrait tre drain de l eau pour pr venir les dommages a...

Page 54: ...od les d int rieur La ventilation pr vue ne d passera pas la longueur maximale pour le nombre de coudes utilis L emplacement d apport r siliation air ventilation pr vues r unit les d gagements L appro...

Page 55: ...t certifi s et r pertori s avec le mod le de chauffage de l eau Le syst me d vacuation doit vacuer directement l ext rieur de l difice et utiliser l air ext rieur pour la combustion viter les trempett...

Page 56: ...de ventilation et resserrez les 4 vis du support Fixez la pi ce de ventilation connect e sur le chauffe eau avec une vis autotaraudeuse dans le trou situ au dessus du collecteur de condensat Support C...

Page 57: ...de condensate Mod les d int rieur V rifiez les habilitations appropri es autour des vents et les prises d air S assurer que vous avez utilis les produits de ventilation correctes pour le mod le insta...

Page 58: ...r 150 PSI 1034 kPa et au moins la valeur maximum de BTU H de l appareil Le d versement venant de la soupape de s ret doit tre amen par tuyau au sol ou dans un syst me de drainage pour viter une exposi...

Page 59: ...building codes Confer with local building officials before installation Tuyauterie recommand e pour installation de base Connexion de gaz en 3 4 po 19 mm Alimentation en gaz Conduite d alimentation e...

Page 60: ...yauterie pour Installation de base 1 Sonder l approvisionnement en eau pour le chauffe eau sur la connexion de MNPT 3 4 au bas de l unit marqu Prise d eau qui est l ap provisionnement en eau froide 2...

Page 61: ...ns quent les pieds cubes par heure 180 000 65 000 1000 245 pi3 H Si la longueur de la conduite est de 10 pieds puis taille du tuyau de 3 4 de pouce est capable de fournir 273 pi3 H de gaz naturel Tout...

Page 62: ...pas r duire ou supprimer l chouement terminal de ce plug Liste de v rification pour gaz et lectricit Une vanne manuelle de gaz est plac e dans la ligne de gaz pour le chauffage de l eau V rifiez les c...

Page 63: ...leurs de temp rature avec le pouvoir Bien que le contr leur est un dispositif de basse tension il y a 120 volts potentiels c t les connexions de contr leur de temp rature l int rieur de l unit Ne se...

Page 64: ...ssez le filtre eau Rincer le filtre supprimer tous les d bris Installez le filtre et ouvrir les vannes d isolement Une vanne manuelle de gaz a t plac e dans la ligne de gaz pour le chauffage de l eau...

Page 65: ...THERMISTANCE D CHA GEUR THERMIQUE THERMISTANCE DE SORTIE D EAU 1 INTERRUPTEUR DE SURCHAUFFE CIRCUIT DE D TECTION DE FLAMME CIRCUIT DE COMMANDE D LECTRO VANNE LECTRODE DE FLAMME 1 RELAIS 1 CIRCUIT DE...

Page 66: ...r vos informations partag es avec ces entreprises veuillez contacter le service client le et demandez ne pas d avoir votre information partag e Nous allons cependant continuer vous contacter avec les...

Page 67: ...a en la tournant fond dans le sens horaire position OFF INSTRUCTIONS DE MISE EN MARCHE 1 ARR TEZ Lisez les instructions de s curit sur la portion sup rieure gauche de cette tiquette 2 R glez le thermo...

Page 68: ...r de MC 91 2 est le contr leur de temp rature standard qui est fourni avec l appareil de chauffage de l eau Sur les mod les de l int rieurs elle est int gr e dans le panneau avant Le contr leur de MCC...

Page 69: ...nts de distribution cette temp rature sauf un changement d sir au point d origine ou n importe quelle commande La temp rature peut tre ajust e entre 98 F 37 C et 110 F 43 C m me en cas de tirage d eau...

Page 70: ...tion de hydronics une soupape m langeant doit tre aussi install e pour limiter la temp rature d eau chaude potable une temp rature s re Arroser des temp ratures plus de 125 F 52 C peut causer des br l...

Page 71: ...tuels S il y a un blocage contactez un professionnel autoris Moteurs Les moteurs sont lubrifi s vie et ne demandent pas de lubrification p riodique Cependant vous devez garder fan et moteur libre de l...

Page 72: ...ns visent sugg rer des pratiques qui sont efficaces pour l apposition du chauffe eau Ils devraient tre utilis s comme un guide uniquement Aucune responsabilit ne suppose pour toute questions d coulant...

Page 73: ...PE DE CIRCULATION SOUPAPE DE VIDANGE DE CHAUDI RE VANNE LECTROMAGN TIQUE POMPE DE CIRCULATION 5 Verser 4 gallons de qualit non dilu d alimentaire vierge vinaigre blanc dans le seau 6 Placez le tuyau d...

Page 74: ...Allumez le pouvoir 7 Apr s avoir confirm que le contr leur de temp rature est tourner sur l approvisionnement en gaz 8 Tourner sur le contr leur de temp rature Traversant un faible volume d eau le ch...

Page 75: ...a main d uvre ou qu il est d termin qu il a t mal install ou endommag pendant l exp dition de retour la r clamation au titre de la garantie pourra tre rejet e 1 La p riode de couverture est r duite 3...

Page 76: ...la cong lation ou toutes forces majeure force majeure Cette Garantie limit e ne s applique pas pour tout produit sur lequel num ro de s rie ou date de fabrication auraient t effac s Cette Garantie lim...

Page 77: ...Value Series Manual 77...

Page 78: ...78 Value Series Manual...

Page 79: ...Value Series Manual 79...

Page 80: ...Commercial Applications ENERGY STAR qualified models Condensing Tankless Water Heaters Up to 0 96 Energy Factor EF Internal or External Installation Pair up with the Rinnai Air Handler for efficient...

Reviews: