Value Series Manual
15
Condensate
(indoor models only)
Condensate formation can occur in high efficiency
direct vent appliances. Without proper drainage
condensate will damage the heat exchanger.
To prevent condensate damage follow these
instructions.
DO NOT
Do not allow condensate to enter the water
heater.
Do not connect the condensate drain pipe directly
to the rain sewer.
Do not connect the condensate drain line with an
air conditioning evaporator coil drain.
MUST DO
Use only vent that is approved and identified as
acceptable for your particular model.
For vertical terminations, install a condensate drain
and trap as close as possible to the appliance.
Slope the venting toward the appliance according
to the vent manufacturers installation instructions.
All condensate must drain and be disposed of
according to local codes.
Use only corrosion resistant materials for the
condensate drain lines such as PVC pipe or plastic
hose.
The condensate drain pipe (along its entire length)
must be at least the same diameter as the drain
line, (5/8 inch NPT).
The end of the condensate drain pipe should be
open to the atmosphere. The end should not be
under water or other substances.
To minimize freezing of the condensate, run the
condensate drain line through an interior wall or
between insulation and an interior wall.
The condensate collector should be used for all
hydronic heating applications.
Checklist for Venting and
Condensate (indoor models only)
□
Verify proper clearances around the vents and air
intakes.
□
Ensure you have used the correct venting
products for the model installed and that you
have completely followed the venting
manufacturer’s installation instructions and these
installation instructions.
□
Verify that the vent pipe has a downward slope or
grade to the outside of 1/4 inch per foot (1.2
°
)
OR if the vent pipe is sloped toward the water
heater (as some local codes require), that a
condensate collector is installed to allow
condensation to drain away from the water
heater to a proper drain source.
□
Verify that condensate will not be allowed to
drain back into the water heater.
□
Verify that the vent system does not exceed the
maximum length for the number of elbows used.
INFORMATION
A condensate trap is available, P/N 222053.
Regions of cold climate will create more
condensate in the vent system. The condensate
collector should be used in cold climates.
The condensate drain pipe should be as short as
possible and have a downward pitch.
Summary of Contents for V65e
Page 27: ...Value Series Manual 27 Ladder Diagram...
Page 77: ...Value Series Manual 77...
Page 78: ...78 Value Series Manual...
Page 79: ...Value Series Manual 79...