- 16 - Rinnai Luminaire® Outdoor Gas Fire - Operation and Installation Manual
Attach metal lintel and angled clearance brackets
Luminaire Outdoor Fire cabinet options are supplied with a metal lintel and angled clearance brackets.
These are required for installations where combustible framing is used.
• Metal lintels
Open One-Sided Cabinet (1), Open See-Through Cabinet (2)
• Angled clearance brackets
Open One-sided Cabinet (4), Open See-Through Cabinet (4)
Metal lintel
Designed to sit about the unit and replace combustible framing in areas exposed to high
temperatures. The minimum distance above the unit to a combustible frame is 500 mm.
To fit
Step 1. Take out and undo four fastenening screws at
either end.
Step
2. Flip side sections 180° and loosely refit
screws.
Step 3. Adjust to desired length before tightening.
Angled clearance brackets
Designed to ensure combustible framing is greater than 25 mm from the sides of the unit as shown.
Top View - Open One-Sided Cabinet
Top View - Open See-Through Cabinet
side sections need to be rotated 180°
and secured into framing above unit.
1225 mm (min)
cabinet
non combustible
cladding
clearance bracket
timber stud
1180 mm (min)
1195 mm (max)
min 500mm
1225 mm (min)
cabinet
non combustible cladding
clearance
bracket
timber stud
1180 mm (min)
1195 mm (max)
470mm
KITSET INSTALLATION - COMBUSTIBLE FRAME