GENERAL INSTALLATION INSTRUCTIONS
HORIZONTAL FLUE TERMINAL CLEARANCES
Extract from AS/NZS 5601
Flue terminal
Fan assisted flue appliance only
Gas meter
Electricity meter or fuse box
Mechanical air inlet
Min. Clearances
(mm)
Fan-Assisted
•
Appliances
up to 50 MJ/h input
200
•
Appliances
over 50 MJ/h input
300
b
From the ground, above a balcony or other surface *
300
c
Front a return wall or external corner *
300
d
From a gas
meter
(M) (see 5.11.5.9 for vent terminal location of
regulator
)
(see Table 6.6 for New Zealand requirements)
1000
e
From an electricity
meter
or fuse box (P) †
500
f
From a drain pipe or soil pipe
75
g
Horizontally from any building structure* = or obstruction facing a terminal
500
h
From any other
flue terminal
, cowl, or combustion air intake †
300
•
Appliances
up to 150 MJ/h input *
300
•
Appliances
over 150 MJ/h input up to 200 MJ/h input *
300
•
Appliances
over 200 MJ/h input up to 250 MJ/h input *
500
•
Appliances
over 250 MJ/h input *
1500
• All fan-assisted
flue appliances
, in the direction of discharge
1500
k
From a mechanical air inlet, including a spa blower
1000
• Space heaters up to 50 MJ/hr input
150
• Other
appliances
up to 50 MJ/hr input
500
•
Appliances
over 50 MJ/h input and up to 150 MJ/h input
1000
•
Appliances
over 150 MJ/h input
1500
1
Where dimensions
c, j
or
k
cannot be achieved an equivalent horizontal distance
measured diagonally from the nearest discharge point of the terminal to the opening
may be deemed by the Technical Regulator to comply.
2
See Clause 6.9.4 for restrictions on a
flue terminal
under a covered area.
3
See Figure J3 for clearances required from a
flue terminal
to an LP Gas
cylinder.
A
flue terminal
is considered to be a source of ignition.
4
For
appliances
not addressed above acceptance should be obtained from the
Technical Regulator.
Ref.
Item
a
Below eaves, balconies and other projections:
FIGURE 6.2 (in-part) MINIMUM CLEARANCES REQUIRED FOR FAN-ASSISTED FLUE TERMINALS, ROOM-
SEALED APPLIANCE TERMINALS AND OPENINGS OF OUTDOOR APPLIANCES
* - unless
appliance
is
certified
for closer installation
n
j
Horizontally from an openable window, door, non-mechanical air inlet, or any other opening into a
building with the exception of sub-floor ventilation:
Vertically below an openable window, non-mechanical air inlet, or any other opening into a
building with the exception of sub-floor ventilation:
NOTES:
† - Prohibited area below electricity meter or fuse box extends to ground level.
Summary of Contents for infinity 26 touch REU-VRM2626WD
Page 1: ......
Page 2: ...This page is intentionally blank...
Page 25: ...Rinnai Australia 25 Installation Manual NOTES...
Page 26: ...Rinnai Australia 26 Operation Manual This page is intentionally blank...
Page 43: ...Rinnai Australia 43 Installation Manual NOTES...
Page 44: ...OIM INFINITY TOUCH 13 031 Issue 1 05 02 14 44 CONTACT INFORMATION...