background image

Rinnai 12 

Split AC IM

DRED Connection (optional)

This appliance is supplied with an DRED interface, the interface provides two connection methods of either a four 

wire terminal connection or an RJ45 socket�

WARNING

Must be installed, maintained and removed by authorised persons in accordance with AS/NZS 

3000 and to all other relevant local regulations and municipal building codes including OH&S 

requirements.

Ensure electric wiring is installed properly. Improper installation may cause malfunction, fire, or 

electric shock.

1�  Remove the wiring cover�
2�  Connect the power feed to the terminal block as shown on the drawing below�
3�  Connect the communication cable to DRED interface using either the four wire terminal connections or RJ45 

socket provided�

4�  Re-install the wiring cover�

Wiring

cover

1 2 3 C

RJ45

DRED

 To Power

To

 D

R

ED

 (4

 w

ire

 in

st

al

la

tio

ty

pe

)

 T

o D

R

ES

 (R

J4

5 in

sta

lla

tio

n ty

pe

)

DCSR

N

S

L

Electrical cable(s)

To Mains  Power

L

N

S

INSTALLATION

Summary of Contents for CJ Series

Page 1: ...tem HSNCJ25B HSNCJ35B HSNCJ50B HSNCJ70B Indoor HINCJ25B HINCJ35B HINCJ50B HINCJ70B Outdoor HONCJ25B HONCJ35B HONCJ50B HONCJ70B REFRIGERANT R32 CJ Series Split Type Wall Mounted Air Conditioner Installation Manual ...

Page 2: ...ons Current AS NZS 3000 AS NZS 5141 Local Regulations and Municipal Building Codes including local OH S requirements This appliance must be installed maintained and removed only by an Authorised Person For continued safety of this appliance it must be installed and maintained in accordance with the manufacturer s instructions ...

Page 3: ... Indoor Unit 9 Wall Mounting Plate 9 Wall Penetration 9 Drain Pipe 9 Electrical Connections 10 Wall Installation 10 Outdoor Unit 11 Electrical Connections 11 DRED Connection optional 12 Condensate Drain Installation 12 Refrigerant Pipes 13 Flaring 13 Connecting Vapour Liquid Pipes To Indoor Outdoor Units 13 Air Purging Leakage Test 14 Evacuation Vacuum Method Leak Test 14 Adding Refrigerant for Lo...

Page 4: ... or unpacking this appliance Failure to do so may result in serious injury or product failure DO NOT modify the electrical wiring of this appliance If the control power wiring is damaged or deteriorated then it must be replaced by an authorised person Failure to do so may result in electric shock fire serious injury or product failure DO NOT install the air conditioner on an unstable or non level ...

Page 5: ... performance Install the drain hose properly for smooth drainage of condensed water Make sure to check for and rectify any refrigerant leaks after you install or repair the unit This appliance uses R32 difluoromethane refrigerant which is a flammable gas class 2 2 according to AS NZS 1677 and must be handled by a refrigeration mechanic with appropriate Australian refrigerant handling licence WARNI...

Page 6: ...liance turn the appliance off isolate the power supply and contact a service agent DO NOT operate the appliance if it has been submerged into water due to flooding contact a service agent Failure to do so may result in electric shock fire serious injury or product failure This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or la...

Page 7: ...rature display the display is built into the front access panel 7 Refrigerant pipes electrical cable s covered with binding tape 8 Condensate drain hose covered with binding tape 9 Refrigerant entry for service and installer use only 10 Outdoor unit air inlet on rear left side of unit 11 Outdoor unit air discharge and protective grille on front of unit WEIGHTS DIMENSIONS Model HSNCJ25B HSNCJ35B HS...

Page 8: ... and plants near the air discharge The clearances shown MUST BE maintained PIPE LENGTH ELEVATION LIMITS Models Pipe Size Gas Pipe Size Liquid Chargeless Length Minimum Length X Maximum Length X Maximum Height Y Additional Refrigerant mm inch mm inch m m m m g m HSNCJ25B Ø9 52 3 8 Ø6 35 1 4 10 2 20 12 15 HSNCJ35B Ø12 7 1 2 Ø6 35 1 4 10 2 20 12 15 HSNCJ50B Ø12 7 1 2 Ø6 35 1 4 10 2 30 20 15 HSNCJ70B ...

Page 9: ...e unit in a place where electrical wiring or conduits are located C B Ø70 A E D Wall Mounting Plate Positioning Dimensions mm HINCJ25B HINCJ35B HINCJ50B HINCJ70B A B C D E A B C D E A B C D E A B C D E 294 881 228 84 43 316 940 218 54 41 316 997 217 43 38 330 1132 236 56 39 Wall Penetration Drill a Ø70mm wall penetration through the wall with a 2 to 4 fall to the outside wall Drain Pipe 1 Connect ...

Page 10: ... the rear of indoor unit as shown 2 Position the piping as shown on the drawing 3 Tape the refrigerant pipes electric cable s and drain hose Ensure the water drain hose is located at the lowest side of the bundle NOTE The drain pipe is dual handed and may be installed to either the left or right of the appliance 1 To use this option unclasp the drain hose 2 Unscrew the rubber plug from the alterna...

Page 11: ...G Must be installed maintained and removed by authorised persons in accordance with AS NZS 3000 and to all other relevant local regulations and municipal building codes including OH S requirements Ensure electric wiring is installed properly Improper installation may cause malfunction fire or electric shock The unit must be earthed following local electrical codes 1 Remove the wiring cover 2 Secur...

Page 12: ...equirements Ensure electric wiring is installed properly Improper installation may cause malfunction fire or electric shock 1 Remove the wiring cover 2 Connect the power feed to the terminal block as shown on the drawing below 3 Connect the communication cable to DRED interface using either the four wire terminal connections or RJ45 socket provided 4 Re install the wiring cover Wiring cover 1 2 3 ...

Page 13: ...bearings etc Prior to assembly refrigeration pipes must be clean and burr free They must not be crushed or kinked For flare connections a suitable lubricant must be used between the back of the flare and the nut to avoid tearing the flare when tightening the nut Connecting Vapour Liquid Pipes To Indoor Outdoor Units 1 Align the centre of the pipes 2 Sufficiently tighten the flare nut with fingers ...

Page 14: ... and run for a minimum of 15 minutes 4 Close low pressure gauge valve manifold gauge set and turn off vacuum pump 5 Wait 2 minutes to allow pressure to stabilise then check that the low pressure gauge is maintaining a pressure of 100 kPa 76 cmHg 6 Disconnect charge hose from the vapour valve service port and replace the vapour valve service port cap 7 Open both the vapour and the liquid valves to ...

Page 15: ...ock or electrical fire Is the wiring in accordance within the specifications Operation failure electrical fire Are all inlets outlets of the indoor and outdoor units free of any obstructions No cooling or heating Are the stop valves open No cooling or heating Are the pipes designed for use with R32 Pipe or pipe connection leakage Has a leak test been carried out for the pipe connections Pipe conne...

Page 16: ...all higher from mobile or public phones For further information visit www rinnai com au or email enquiry rinnai com au Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai appliance If your appliance requires service please call our National Help Line Rinnai recommends that this appliance be serviced every 3 years Wi...

Reviews: