6 Operations and Functions
6-1. Gas alarm activation
SD-1DGH-AS
- 36 -
6
Operations and Functions
6-1. Gas alarm activation
Gas alarm: Triggered when the concentration of detected gas reaches or exceeds the alarm setpoint value.
<<Auto-Reset>>
NOTE
The alarm setpoint is factory-set. Although the alarm delay time (standard: 2 seconds) works in the
detector to prevent a false activation, it can be cancelled if not needed.
<Display Operation>
Gas Concentration Display
In case of over the detection range (Over Scale), "
∩∩∩∩
" is displayed on the LED.
Power Indicator Lamp (POWER: Green)
During operation, this lights up continuously.
Alarm Indicator Lamp (ALM: Red)
It lights up when the alarm setpoint value is reached to or exceeded.
<Contact Activation>
The contact is activated when the gas concentration reaches or exceeds the alarm setpoint value. (only
when the alarm is used)
The contact activation is reset automatically when the gas concentration drops below the alarm setpoint
value.
Alarm delay time (2 seconds)
Alarm lamp (ALM)
Alarm contact (terminal plate 4, 5)
Alarm setpoint
C
onc
en
tr
ation
0
Time
Summary of Contents for PT2-169
Page 1: ...PT2E 2525 Smart Transmitter Gas Detector Head SD 1DGH AS Operating Manual PT2E 170 PT2 170...
Page 4: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 12: ......
Page 15: ......
Page 19: ......
Page 20: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 28: ......
Page 29: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 38: ......
Page 43: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 62: ...10 Product Specifications 10 1 List of specifications SD 1DGH AS 62 Outline Drawings...
Page 65: ......