6.MAINTENANCE AND INSPECTION 

 
Gas detection and alarm instrument is kept in continuous operation over a long time and must     
perform a vital role as a safety device.    For this purpose, periodical inspection must be made.   
The High-pressure Gas Safety Act in Japan sets forth the obligation of periodical inspection of 
the gas detection and alarm instrument.   
 

- Maintenance Contract – 

Be  sure  to  perform  the  regular  maintenance  inspection  since  this  is  an  instrument  for 
security and safety.    If this detector head founds defective, contact our nearest agent or 
RIKEN KEIKI soon. 

 
6-1.Inspection frequency and items 

The inspection includes a daily inspection which a person in charge of control and operation of 
the  gas  detection  instrument  performs  inspection  before  work  once  a  day,  and  a  monthly 
inspection  carried  out  once  a  month,  and  periodical  inspections  conducted  by  the  service 
personnel  designated  by  manufacturer.  The  inspection  items  are  confirmation  of  lights, 
concentration indication and alarm function on the indicator/alarm unit side. It is also necessary 
to carry out gas calibration at least every 6 months. The law in Japan sets forth that the unit 
must  issue  an  alarm  during  the  circuit  inspection  related  to  alarm  while  providing  normal 
operation, at least, once a month. 
To maintain the safety operation of the gas detection instrument, it is recommended to keep 
the maintenance contract with our authorized distributor for regular maintenance, adjustment 
and overhaul etc including the gas sensitivity adjustment (gas calibration).   
For the detail of maintenance contract, contact our nearest agent or RIKEN KEIKI. 
 

 

 

・This is a safety instrument and the inspection every 6 months or more is 

mandatory  to  ensure  the  safety.    If  the  unit  is  used  by  continuously 
without inspection, the sensor sensitivity may change, resulting in failure 
of correct detection. 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING 

                                    * NOTE 

・Be sure to inform sections concerned beforehand when performing   
  alarm test or gas calibration.    For the equipment connected with output   

signal from indicator/alarm unit, perform them after disconnecting the   
output signal. 

・Special trained engineer for gas detection instrument can perform 

maintenance work and inspection accurately and efficiently. Then, it is 
recommended to contact our authorized agent for maintenance and 
inspection. 

Summary of Contents for GD-F3A-SC-A

Page 1: ...Oxygen Gas Detector Head GD F3A SC A Operating Manual PT2 150 PT2E 2490...

Page 2: ...tor head 2 Alarm level for gas alarm instrument shall be set within the performance of the instrument Our standard alarm level is 18 by volume for the prevention of oxygen deficiency 3 This is not con...

Page 3: ...le 10 Example of cable connection 10 OPERATION METHOD Preparation before start up 12 Start up 12 Stopping the operation 12 MAINTENANCE AND INSPECTION Inspection frequency and items 13 Calibration Requ...

Page 4: ...L CASE Responding to trouble alarm 18 Before it is thought to be a trouble 18 PRODUCT SPECIFICATIONS Standard specifications 19 Standard accessories 19 Optional accessories 19 Detection principle 20 D...

Page 5: ...esigned as drip proof construction for outdoor installation Also it can be used as intrinsically safe system in combination with zener barrier option to be able to install in hazardous area Identifica...

Page 6: ...nterval Do not change or remodel the circuit structure of this unit Do not disassemble the sensor since there is a electrolyte inside If your finger touches the electrolyte wash your finger away with...

Page 7: ......

Page 8: ...11mm from outside Hinge Hinge for front door Lock Lock for front door Mounting hole Mounting hole to fix this unit on the wall surface Terminal strip 2 Relayed terminal for input output signal use to...

Page 9: ...apacitance Co of intrinsic safety circuit and external wiring inductance Lw and capacitance Cw of intrinsic safety circuit Lo Li Lw Co C Cw 3 When making wiring connection for intrinsic safety circuit...

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ...cable For system installation operation and maintenance take care not to damage the intrinsically safe design The power of the indicator alarm unit shall be turned on after completion of all wirings...

Page 14: ...ted correctly this system starts operation by putting on the power switch in indicator alarm unit Be sure to perform gas calibration at the time of new installation Correct reading may not be obtained...

Page 15: ...cessary to carry out gas calibration at least every 6 months The law in Japan sets forth that the unit must issue an alarm during the circuit inspection related to alarm while providing normal operati...

Page 16: ...the supply of zero gas disconnect calibration adapter and confirm that the oxygen reading returns to 20 9vol Completion of zero adjustment Performing a span adjustment Plug the ammeter lead into termi...

Page 17: ......

Page 18: ...sor Environment of low temperature 5 10 Environment of low oxygen content Put a sensor into the container and seal off the container List of recommendable spare parts for regular replacement No Name o...

Page 19: ...etector head is relocated select a new place in accordance with 4 2 Installation place and 4 4 Installation works For information on wiring work see 4 5 Caution at wiring construction The unpowered ti...

Page 20: ...agent or RIKEN KEIKI Before it is thought to be a trouble Check the wirings around the related instruments as well as this detector head It may be caused by improper operation Re check the detection...

Page 21: ...m unit Zener barrier MTL7728ac MTL7728 MTL7728 ZB 1A ZB 1A ZB 1A ZB 4A ZB 4A ZB 4A Cable entry Cable gland Applicable cable O D 8 11mm Operating temperature 10 40 non rapidly vary Operating humidity L...

Page 22: ......

Page 23: ...r Safety retainer for explosion protection by limiting the energy of electric current within a non ignition level CVVS This is a kind of connecting cable between indicator alarm unit and oxygen detect...

Page 24: ...Manual Log Rev Amendment Issue data 0 First issue 2018 1 9...

Reviews: