24
For the conversion from methane gas to LPG, install the burner flange
(H).
For the conversion from LPG to methane gas, remove it.
b
Before removing the burner flange, empty the water heater as
described in the paragraph "Emptying the water heater".
H
Then set
Parameter 4
(see paragraph "Parameters menu") as follows:
Conversion from METHANE to LPG
Parameter
Value
4
1
Conversion from LPG to METHANE
Parameter
Value
4
0
10.1 Adjustments
The appliance has already been factory set by the manufacturer.
However, should it need to be readjusted, for example after non-sched-
uled maintenance, replacing the gas valve or gas conversion, proceed
as described below.
b
Adjustments to maximum power must be performed in the indi-
cated sequence and only by qualified technicians.
-
Remove the casing by unscrewing the fixing screws
A
(see sec-
- Loosen the screw of the pressure test point (1) downstream from
the gas valve by roughly two turns, then connect the pressure
gauge
- Disconnect the compensation connector (5) from the gas valve
- Remove the protective hood (2)
-
Open a water tap to its maximum flow rate, set the temperature
selector to maximum and power up the water heater
1
5
2
3
4
Adjusting to the maximum value:
- Screw the nut (3) fully on until obtaining the gas pressure shown
in the table
Maximum gas pressure at nozzles
G20
15,20
mbar
155,00
mm. W.C.
LPG
35,30
mbar
359,96
mm. W.C.
Adjusting to the minimum value:
- disconnect one of the two electric cables from the coil
- screw or unscrew the hex head socket screw (4) to adjust the
minimum until obtaining the gas pressure value shown in the
table
- put back the protective cap (2)
Minimum gas pressure at nozzles
G20
2,10
mbar
21,41
mm. W.C.
LPG
5,00
mbar
50,99
mm. W.C.
- Reconnect the compensation socket to the gas valve (5)
- Disconnect the pressure gauge and re-tighten the pressure test
point screw (1)
b
Please remember that for operation with LPG, the appliance
needs a gas supply pressure adjuster, which should be set to
37 mbar.
b
Please remember that for operation with LPG, a gas pressure
regulator at the appliance power supply is required, set to 37
mbar for propane.