38
INSTALLATION
Menu Par.
No.
Nr. dis-
played
Display
Description
Range
Default set-
ting
UM
Access
type
Category
M1
139
Dair active
Activates bleeding the system's air. To activate air
bleeding, it is necessary to switch on the boiler
and change the parameter from "No" to "Yes".
Wait for one minute. Switch off and restart. At this
stage, when it is restarted the boiler will initiate
the automatic bleeding procedure (lasting around
20 minutes). With the parameter set to "Yes", the
procedure is carried out each time the boiler is
switched off and restarted using its master switch.
The value must be set to "No" if you do not wish to
initiate the bleeding procedure when the thermal
module is switched on.
Yes
No
No
I
General
M1
140
Minimum
Flow
Defines the flow rate below which the boiler is
switched off. The value varies depending on the
model.
0.0…100
Depends on
boiler model
l/min
I
General
M1
107
Anti-Le-
gionella day
Sets the weekday on which the anti-Legionella
procedure is carried out.
Sunday...
Saturday
Sunday
Day
I
DHW
M1
108
Anti-Le-
gionella
Hour
Sets the time of the day during which the anti-Le-
gionella procedure is carried out.
0…23
0
Time
I
DHW
M1
155
Frost Pro-
tection
Defines the delivery temperature below which the
thermal unit pump and the system pump (with
cascade configuration) are activated if. If the tem-
perature of one of the delivery sensors (excluding
the zone sensors) falls another 5 degrees below
the value set by Par. 155, then a request to activate
the cascade is generated. When the temperature of
the primary sensor reaches five degrees above the
value defined by Par. 155, then the request ceases
and the cascade returns to stand-by mode.
10...30
15
°C
I
Cascade
M1
186
Frost pro-
tection out
If the temperature outside is below the value set
in this parameter, the thermal unit pump (PC), the
system pump (PS), and the central heating system
pump (PI) are activated
-30…15
5
°C
I
Cascade
M1
189
Burner
Address
Not usable
-
-
-
Cascade
M1
191
Fan Type
Defines the type of fan installed in the thermal unit
Do not
change. Use
permitted only
to authorised
service centres
Changes
based on the
configuration
of Par. 97
I
General
M1
205
Dep. Zone
Control
Enables control of the additional heating zone
managed by the Depending thermal unit
0 = Disabled
1 =Enabled
0…1
0
U
General
M2
72
Permit
Emergency
Mode
Activates the emergency mode. This mode comes
on when communication between Managing and
the primary circuit's probe is lost. In this event,
if Par. 72 is set to "Yes", the cascade is initiated,
working to the fixed set-point determined by Par.
74.
Yes
No
Yes
U
Cascade
M2
74
Emergency
Set-point
Set-point active in emergency mode.
20…70
70
°C
I
Cascade
M2
75
Delay Per
Start Next
Mod.
Defines the stand-by time in seconds to restart the
subsequent cascade module in normal start mode.
5…255
120
Sec.
I
Cascade
M2
76
Delay Per
Stop Next
Mod.
Defines the stand-by time in seconds to switch off
the last cascade module on in normal Off mode.
5…255
30
Sec.
I
Cascade
M2
142 Delay Quick
Start Next
Defines the stand-by time in seconds to restart the
next cascade module in quick start mode.
5…255
60
Sec.
I
Cascade
M2
143 Delay Quick
Stop Next
Defines the stand-by time in seconds to switch off
the last cascade module on in Quick Stop mode.
5…255
15
Sec.
I
Cascade