GENERALE

 

b)

 

EXEMPTIONS

: The following equipment is exempt from 248 CRM 

5.08(2)(a) 1 through 4:

 

− The equipment listed in Section 10 entitled “Equipment Not 

Required To Be Vented” in the most current edition of NFPA 

54 as adopted by the board;

 

− Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from 

the dwelling, building or structure used in whole or in part 

for residential purposes.

c)

 

MANUFACTURERS REQUIREMENTS - GAS EQUIPMENT VENTING SY-

STEM REQUIRED

: When the manufacturer of Product Approved side 

wall horizontally mounted gas equipment provides a venting sy-

stem design or venting system components with the equipment, 

the instructions provided by the manufacturer for the installation 

of the equipment and venting shall include:

 

− Detailed instructions for the installation of the venting sy-

stem or the venting system components;

 

− A complete parts list for the venting system design or ven-

ting system.

d)

 

MANUFACTURERS REQUIREMENTS - GAS EQUIPMENT VENTING SY-

STEM NOT PROVIDED

: When the manufacturer of Product Approved 

side wall horizontally vented gas fueled equipment does not pro-

vide the parts for the venting of flue gases, but identifies “special 

venting systems”, the following requirements shall be satisfied by 

the manufacturer:

 

− The referenced “special venting systems” shall be included 

with the appliance or equipment installation instructions;

 

− The “special venting systems” shall be Product Approved by 

the Board and the instructions for that system shall include 

a parts list and detailed installation instructions.

e)

 A copy of all instructions for all Product Approved side wall ho-

rizontally vented gas fueled equipment, all venting instructions, 

all parts lists for venting instructions and/or venting design in-

structions shall remain with the appliance or equipment at the 

completion of the installation.

1.10 

Combustibili idonei

Permissible fuels

 

− Natural gas from the public gas supply in accordance with 

national regulations with a total sulphur content < 15ppm.

 

− LP in accordance with national regulations with a content 

of elementary sulphur < 1.5 ppm and volatile sulphur < 50 

ppm.

 

− Ultra Low Sulphur Diesel in accordance with national regu-

lations with a content of elementary sulphur < 15 ppm (for 

use as back-up fuel in condensing operation).

 

− Heating oil type 2 when boiler return temperature is not 

lower than 140 degrees Fahrenheit; non-condensing ope-

ration (for use as backup fuel only). See the warranty state-

ment for additional details.

 

9

Do not use gasoline, crankcase drainings, or any oil contai-

ning gasoline.

 

− The boiler must only be operated with the specified fuels.

 

− Only burners that are suitable for the specified fuels may 

be used.

 

− Observe the manufacturer's burner selection list and the 

burner manufacturer's instructions.

1.11 

Bruciatori

Follow  the  burner  manufacturer’s  instructions when  fitting  the 

burner. A pre-drilled burner plate is included with the boiler.

An accessory plate may be required if a non-standard burner is 

used (see table).

As standard, the burner plate gasket must be trimmed in order to 

fit the burner blast tube.

The installer must cut the hole 3/8" larger than the blast tube dia-

meter.

The combustion chamber door must be opened to allow the bur-

ner to be mounted.

If  the  burner  head  is  too  long  to  open/close  the  combustion 

chamber door, the burner have to be removed before to open/

close the door.

For reduction of burner capacity according to altitude make refe-

rence to the burner manual.

 

9

When you finish installing the burner, fill the gap between the 

burner tube and the refractory material in the door with the 

ceramic insulation supplied loose with the boiler.

RTC 3000

RTC 4000

RTC 5000

Fireside 

pressure 

drop

inch 

W.C.

2.088

2.931

3.011

mbar

5.2

7.3

7.5

RTC 6000

RTC 8000

RTC 10000

Fireside 

pressure 

drop

inch 

W.C.

3.533

3.693

4.777

mbar

8.8

9.2

11.9

At maximum output with water temps supply/return of 176/140 °F 

(80/60 °C) and CO2=9.7%.

1.11.1 

Bruciatori consigliati per l'abbinamento

BRUCIATORI

BOILERS

MODELLO

RTC 

3000

RTC 

4000

RTC 

5000

RTC 

6000

RTC 

8000

RTC 

10000

GAS

RS100/M

x

RS130/M

x

RS190/M

RS100/E

x

RS130/E

x

RS190/E

RS280/E

x

RS300/E

x

RS310/E

RS400/E

RS100/EV

x

RS130/EV

x

RS190/EV

RS280/EV

x

RS300/EV

x

RS310/EV

RS400/EV

RS68/E

x

Summary of Contents for RTC Series

Page 1: ...cod 20112713 rev 6 08 2017 RTC 3000 4000 5000 6000 RTC 8000 10000 RTC IT ISTRUZIONI PER IL RESPONSABILE DELL IMPIANTO PER L INSTALLATORE E PER IL SERVIZIO TECNICO DI ASSISTENZA...

Page 2: ...o fornirLe le informazioni che ri teniamo necessarie per una corretta e pi facile installazione dell apparecchio senza voler togliere nulla alla Sua competenza e capacit tecnica Buon lavoro e rinnovat...

Page 3: ...g old heating systems 22 2 6 7 Elimination air and gas from central heating system 22 2 6 8 Use of Antifreeze 22 2 7 Impianti idraulici di principio 23 2 8 Evacuazione della condensa 30 2 9 Neutralizz...

Page 4: ...9 9In caso di fuoriuscite d acqua scollegare la caldaia dalla rete di alimentazione elettrica e chiudere l alimentazione idrica 9 9Verificareperiodicamentechelapressionedieserciziodell im pianto idrau...

Page 5: ...or death from fire Do not use flammable or combustible material in the boiler room It is recommended not to store any items within 16 inches 415mm of the appliance 9 9CAUTION Appliance damage from co...

Page 6: ...L apertura del portello anteriore ambidestra ed possibile an che senza togliere il bruciatore L apertura di fabbrica da sinistra a destra ma pu essere modificata in base alle necessit in in stallazion...

Page 7: ...ruciatore 2 Visore fiamma con presa di pressione 3 Portello 4 Pannellatura 5 Mandata impianto 6 Attacco valvola di sicurezza 7 Ritorno impianto AT 8 Camera di combustione 9 Ritorno impianto BT 10 Cass...

Page 8: ...esa di pressione 3 Portello 4 Pannellatura 5 Mandata impianto 6 Attacco valvola di sicurezza 7 Ritorno impianto AT 8 Camera di combustione 9 Ritorno impianto BT 10 Cassa fumi 11 Raccordo canale da fum...

Page 9: ...low GPM 360 550 650 750 1150 1250 Water Volume gal 354 420 489 597 951 1255 Water Pressure Drop 1 7 psi at 300GPM 0 7 psi at 400GPM 0 6 psi at 500GPM 1 3 psi at 600GPM 1 1 psi at 800GPM 0 8 psi at 100...

Page 10: ...afety limits Value Maximum allowable temperature 210 F 99 C Maximum Allowable Working Pressure MAWP 160 psi 11 bar Maximum cycle time for safety tempe rature limiter 40 s Maximum cycle time for temper...

Page 11: ...n accordance with national regulations with a content of elementary sulphur 1 5 ppm and volatile sulphur 50 ppm Ultra Low Sulphur Diesel in accordance with national regu lations with a content of elem...

Page 12: ...LO RTC 3000 RTC 4000 RTC 5000 RTC 6000 RTC 8000 RTC 10000 GAS RS100 M x x RS130 M x x RS190 M x x RS100 E x x BRUCIATORI BOILERS MODELLO RTC 3000 RTC 4000 RTC 5000 RTC 6000 RTC 8000 RTC 10000 RS130 E...

Page 13: ...able are shown the codes for the upper door kit that shall be ordered as accessory for some matching boiler bur ner BRUCIATORI BOILERS MODELLO RTC 3000 RTC 4000 RTC 5000 RTC 6000 RTC 8000 RTC 10000 RX...

Page 14: ...pleta degli accessori di montaggio pro tetta da un imballo in cartone e da una gabbia di legno 9 9Il libretto di istruzione parte integrante dell apparecchio e quindi si raccomanda di recuperarlo di l...

Page 15: ...RTC 5000 RTC 10000 non sono posizionati su un pallet A rimuovere le viti di fissaggio al pallet mod RTC 3000 RTC 4000 e posizionare la caldaia nel luogo stabilito 0 0 vietato disperdere nell ambiente...

Page 16: ...ght of the lid of the system s condensate neutralizer The gas supply pipe should be installed in such away that the boi ler s paneling can be removed and the front door opened without having to remove...

Page 17: ...3 150 3 150 4 150 4 150 6 150 6 150 DN 3 Ritorno BT 4 150 6 150 6 150 6 150 8 150 8 150 DN 4 Attacco valvola di sicurezza 2 NPT 2 NPT 2 NPT 2 NPT 2 NPT 2 NPT DN 5 Scarico condensa 1 1 4 NPT 1 1 4 NPT...

Page 18: ...m 7 5 190mm 2 5 63mm 7 5 190mm 2 5 63mm 7 5 190mm 3 LWCO 1 2 NPT 2 5 63mm 3 5 89mm 2 5 63mm 3 5 89mm 2 5 63mm 3 5 89mm 2 5 63mm 3 5 89mm 4 Drum temp LF Hold 1 2 NPT 2 5 63mm 4 5 110mm 2 5 63mm 4 5 110...

Page 19: ...NPT 2 5 63mm 9 5 240mm 2 5 63mm 9 5 240mm 3 LWCO 1 2 NPT 2 5 63mm 3 5 89mm 2 5 63mm 3 5 89mm 4 Drum temp LF Hold 1 2 NPT 2 5 63mm 3 5 89mm 2 5 63mm 3 5 89mm 5 Inlet operating temperature sensor 1 2 NP...

Page 20: ...co Portata Perdita di carico GPM psi GPM psi GPM psi GPM psi RTC 3000 276 1 48 184 0 82 138 0 55 92 0 33 RTC 4000 368 0 61 245 0 38 184 0 28 123 0 18 RTC 5000 460 0 56 307 0 34 230 0 25 153 0 16 RTC 6...

Page 21: ...ating system includes an open expansion vessel then the boiler itself must be separated from the heating system by means of a heat exchanger Se la durezza dell acqua di partenza supera il valore indic...

Page 22: ...iciency 2 6 7 Elimination air and gas from central heating system When designing new heating systems it is necessary to eliminate the air and other gases that form in the system Recently added fill or...

Page 23: ...o condi zionate con opportuni sistemi di trattamento Come valori di riferimento possono essere considerati quelli riportati nella tabella del paragrafo Requisiti qualitativi dell acqua 0 0 vietato far...

Page 24: ...re impianto 5 Valvole non ritorno 6 Valvola di sfiato automatico 7 Valvola di sicurezza caldaia 7 Seconda valvola di sicurezza caldaia solo per RTC 8000 RTC 10000 8 Rubinetto di scarico caldaia 9 Filt...

Page 25: ...zionamento 4 Circolatore impianto 5 Valvole non ritorno 6 Valvola di sfiato automatico 7 Valvola di sicurezza caldaia 7 Seconda valvola di sicurezza caldaia solo per RTC 8000 RTC 10000 8 Rubinetto di...

Page 26: ...mento 4 Circolatore impianto 5 Valvole non ritorno 6 Valvola di sfiato automatico 7 Valvola di sicurezza caldaia 7 Seconda valvola di sicurezza caldaia solo per RTC 8000 RTC 10000 8 Rubinetto di scari...

Page 27: ...atore impianto 5 Valvole non ritorno 6 Valvola di sfiato automatico 7 Valvola di sicurezza caldaia 7 Seconda valvola di sicurezza caldaia solo per RTC 8000 RTC 10000 8 Rubinetto di scarico caldaia 9 F...

Page 28: ...mpianto 5 Valvole non ritorno 6 Valvola di sfiato automatico 7 Valvola di sicurezza caldaia 7 Seconda valvola di sicurezza caldaia solo per RTC 8000 RTC 10000 8 Rubinetto di scarico caldaia 9 Filtro a...

Page 29: ...latore impianto 5 Valvole non ritorno 6 Valvola di sfiato automatico 7 Valvola di sicurezza caldaia 7 Seconda valvola di sicurezza caldaia solo per RTC 8000 RTC 10000 8 Rubinetto di scarico caldaia 9...

Page 30: ...azione tale da evitare qualsiasi accumulo di conden sa Pcc in inch W C 1 3 3 7 2 9 Neutralizzazione della condensa raccomandato installare sempre un kit di neutralizzazione della condensa Nella tabell...

Page 31: ...2 towards the boiler All condensate should be treated through a neutralization media before being eliminated to the floor drain 3 2 3 1 RTC 3000 RTC 4000 RTC 5000 RTC 6000 e A RTC 8000 RTC 10000 e A...

Page 32: ...getation Vertical Terminations Roof penetrations should follow all appliance codes and the vent manufacturer s instructions The vent should never be installed at less than the required clearances to c...

Page 33: ...all be located as follows top louver shall start within 12 of the ceiling and the bottom louver within 12 of the floor as prescribed in NFPA 54 2 10 5 Condensate Removal The exhaust vent pipe must be...

Page 34: ...ste in fabbrica con il portello che si apre da sinistra verso destra Qualora sia necessaria l apertura nel sen so opposto operare come segue dopo aver rimosso il pannello laterale Portello RTC 3000 RT...

Page 35: ...rniera superiore Allentare il dado 4 e rimuovere l anello elastico 5 Rimuovere il perno passante 6 4 6 5 Rimuovere i quattro dadi 7 ed estrarre la staffa 8 8 7 Operando in maniera inversa a quanto des...

Page 36: ...opportune di mensioni secondo la legislazione vigente nel paese di in stallazione stringere nuovamente il dado con rondella 1 sul punto di connessione collegare l altra estremit del filo di messa a t...

Page 37: ...ei passacavi ovali del quadro di comando Il quadro di comando non fornito a corredo 3 2 Agganciare i pannelli laterali 2 3 4 5 6 7 ai longheroni superiori 1 della caldaia facendo attenzione a far entr...

Page 38: ...ella pannellatura procedere come riportato in seguito Aprire le asole pretranciate poste sul pannello laterale 3 o 4 a seconda del lato su cui si desidera installare il quadro di comando in corrispond...

Page 39: ...ssare n 8 perni AVP sui fori della parte anteriore dei pan nelli 9 10 11 12 due per pannello e montare i pannelli su periori 11 9 10 12 Agganciare il pannello posteriore superiore 13 nei perni predisp...

Page 40: ...oli la teralmente e agganciandoli sui perni dei pannelli superiore e inferiore 15 16 Montare il profilo anteriore 17 agganciandolo sui perni dei pannelli superiori 17 2 14 Accessorio supporto quadro e...

Page 41: ...emperature and low temperature For an optimum energy yield we recommend supplying a flow rate of 10 of the total nominal flow rate via the low temperature flange with a return temperature below the de...

Page 42: ...slowly and observe the pressure gauge whilst doing so Vent the heating system via the radiator air vent valves If the water pressure drops as a result of venting the system Top up the system with wat...

Page 43: ...tightness Start the burner Complete the burner test report regarding the individual output stages Conduct a tightness test on the hot gas side After a short time in operation tighten the screws in th...

Page 44: ...system re mains operational especially when there is a risk of frost 9 9NOTICE Always keep the oil supply valve shut off if the burner is shut down for an extended period of time 4 1 Shutting down th...

Page 45: ...commencing any main tenance The results of flue gas analysis can give a clear idea of what servi cing or repairs are needed 5 3 Apertura portello Per aprire il portello sufficiente svitare completamen...

Page 46: ...n the heating sy stem The fill and top up water quality must comply with the water re quirements in this manual Air pockets may form in the heating system through the fill or top up water releasing ga...

Page 47: ...lmente la caldaia prima di aprire le aperture di ispezione Le aperture di ispezione sono situate nei seguenti punti Modelli RTC 3000 RTC 4000 RTC 5000 RTC 6000 2 1 1 Ispezione 2 Ispezione e scarico fa...

Page 48: ...if requi red Check and clean the burner Visual inspection and remove any conta mination Check all safety equipment safety shut down Function check Flue gas analysis with test report for each output s...

Page 49: ...e circuit Check the vent valve The boiler has reached the set tempera ture but the radiators are still cold Air in the circuit Bleed the circuit Pump malfunctioning Check release the pump Problem with...

Page 50: ...t the environment we use the best possible technology and materials taking into account economic points of view Packaging For the packaging we participate in the country specific recycling systems whi...

Page 51: ...51...

Page 52: ...setts U S A 02043 2165 Meadowpine Blvd Mississauga Ontario Canada L5N 6H6 www rielloboilers com Poich l Azienda costantemente impegnata nel continuo perfezionamento di tutta la sua produzione le carat...

Reviews: