![Riello RS 500/E LN Installation, Use And Maintenance Instructions Download Page 8](http://html1.mh-extra.com/html/riello/rs-500-e-ln/rs-500-e-ln_installation-use-and-maintenance-instructions_1459886008.webp)
20008423
6
GB
Technical description of the burner
3.1
Technical data
(1)
Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394” wc - Altitude 329 ft.
(2)
Pressure at test point 5) (Fig. 5), with zero pressure in the combustion chamber, and maximum burner output
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated
output.
*
Firing rate for C-ETL Canadian Listing
LIST OF AVAILABLE MODELS
3
Technical description of the burner
Model
RS 300/E LN
RS 400/E LN
RS 500/E LN
Output
(1)
max.
kW
MBtu/hr
1500 - 4220 (3834*)
5112 - 14390 (13082*)
2000 - 4995 (4541*)
6817 - 17043 (15494*)
2715 - 5740 (5217*)
9468 - 19580 (17800*)
min.
kW
MBtu/hr
555
1893
888
3030
1100
3787
Fuel
- max. delivery
- pressure at max. delivery
(2)
SCFH
“ wc
Natural gas
14070
7
Natural gas
16654
13
Natural gas
19138
15
Operation
Low - high or modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °C)
Combustion air temperature
°F max
140 (60 °C)
Noise levels
(3)
dBA
82
85
88
Designation
Electrical supply
Starting
Code
RS 300/E LN
TC
230V-60Hz
Direct
20011898
460V-60Hz
575V-60Hz
-
RS 400/E LN
TC
460V-60Hz
Star/Delta
20011900
575V-60Hz
-
RS 500/E LN
TC
460V-60Hz
Star/Delta
20011902
575V-60Hz
-