20068131
10
GB
Technical description of the burner
4.6
Maximum dimensions
The dimensions of the burner are shown in Fig. 1.
Bear in mind that inspection of the combustion head requires the
burner to be opened and the rear part drawn back on the guides.
The dimensions of the open burner are indicated by position O.
Tab. E
(1) Blast tube: short-long
4.7
Firing rates
The
maximum output
is chosen within area A.
The
minimum output
must not be lower than the minimum limit
of the diagram:
RS 34/E MZ = 45 kW
RS 44/E MZ = 80 kW
Fig. 1
D3831
mm
A
D
E
F
(1)
H
I
L
O
N
V
M
RS 34/E MZ
442
422
508
216-351
140
305
138
780
84
177
1”1/2
RS 44/E MZ
442
422
508
216-351
152
305
138
780
84
177
1”1/2
WARNING
The firing rate (Fig. 2) was obtained considering a
room temperature of 20°C and an atmospheric
pressure of 1013 mbar (approx. 0 m above sea
level), with the combustion head adjusted as
shown at page 24.
Fig. 2
D9304
Thermal power
Thermal power
Combustio
n ch
amber
pressure -
mbar
C
omb
us
tion
c
ha
mb
er
pressure -
mbar
RS 44/E MZ
RS 34/E MZ
Summary of Contents for RS 34/E MZ
Page 2: ...Translation of the original instructions ...
Page 65: ...63 20068131 GB Appendix Electrical panel layout RS 34 E MZ ...
Page 66: ...20068131 64 GB Appendix Electrical panel layout RS 44 E MZ ...
Page 67: ...65 20068131 GB Appendix Electrical panel layout RS 44 E MZ 3Ph ...
Page 68: ...20068131 66 GB Appendix Electrical panel layout RS 34 44 E MZ ...
Page 69: ...67 20068131 GB Appendix Electrical panel layout RS 44 E MZ 3Ph ...
Page 70: ...20068131 68 GB Appendix Electrical panel layout ...
Page 71: ...69 20068131 GB Appendix Electrical panel layout ...
Page 72: ...20068131 70 GB Appendix Electrical panel layout ...
Page 73: ...71 20068131 GB Appendix Electrical panel layout ...
Page 75: ......